EACIE Evacuation Alert Control and Indicating Equipment
Maintenance controls:
Connections
Connections:
Expansion connections:
EACIE Panel Programming Module
Control / Display module:
Mechanical
Protective cabinet overall dimensions (mm):
Protective cabinet weight (empty):
Protective cabinet construction & finish:
Protective cabinet locking system:
Keys (carried by registered key holder):
Protective cabinet compliance:
EACIE panel overall dimensions (mm):
EACIE panel weight (excluding batteries):
EACIE panel weight (including batteries):
Environmental
Operating temperature:
Maximum humidity:
Protective cabinet IP Rating (to EN 60529):
Appendix 6 – Glossary of Terms
AL1: Access Level 1 (for general users).
AL2: Access Level 2 (for authorised users).
AL3: Access Level 3 (for authorised systems engineers).
ARC: Alarm Receiving Centre.
BS 7671: IET Wiring Regulations.
BS 8629:2019: Evacuation Systems for Fire & Rescue Services. Code of practice for the design, installation,
commissioning and maintenance of evacuation alert systems for use by fire and rescue services in buildings
containing flats.
EACIE: Evacuation Alert Control & Indicating Equipment. Component of an evacuation alert system through
which evacuation alert devices (sounders) can be controlled, and that is used to monitor the correct functioning
of the system and give audible and visible warning of any faults.
EAS: Evacuation Alert System. Comprises of evacuation alert devices, sounder controllers and an EACIE
panel with manual controls for the FRS to activate the evacuation alert devices.
EN 54-2: Fire Detection and Fire Alarm Systems. Control and Indicating Equipment.
EN 54-3: Fire Detection and Fire Alarm Systems. Sounders.
EN 54-4: Fire Detection and Fire Alarm Systems. Power Supply Equipment.
Evacuation Alert Device (sounder): Component of the evacuation alert system, not incorporated in the
EACIE, which is used to signal to the occupants of a flat that evacuation is required by the FRS.
Evacuation Alert Zone: May contain flats, part floors, or a complete floor of a building.
FRS: Fire & Rescue Service.
Page 37 of 38  Approved Document No. DFU5030020 Rev 1  Installation and Programming Manual
Interactive touchscreen with menu sensitive buttons. 1 keyswitch provides entry to Access Level 2
Fixed and plug-on connectors, largest acceptable conductor size 2.5mm
RS485 peripheral bus connection allows the connection of up to 15 'A-Bus' PCBs (2 control cores plus screen
plus 2 cores for power).
Control/Display module c/w LCD, touchscreen, keyswitch, 16 LEDs.
700 (H) x 741 (W) x 200 (D)
69kg
Silver grey steel RAL 9006 silver grey epoxy paint
Lock certified to EN 1303
"N" High Security keys included
STS 205 Issue 4/BR2 BMTrada Certificate
442 (H) x 431 (W) x 153 (D) including toggle switch heights
7.5 - 10kg (model dependent)
20 – 22.5kg (model dependent)
-10°C to +40°C
95 % non-condensing
IP30
2
Part No. Z41/CA.