Emerson SolaHD SDU AC B-Series User Manual page 18

Uninterruptible power supply
Table of Contents

Advertisement

SDU AC-B Series
A272-353 Rev. 1 2/2021
Safety
EMC
10.1 Battery Runtime
The UPS has an internal 12V sealed Valve Regulated Lead Acid (VRLA) rechargeable battery.
Models
VA/Watts
CSB XTV 1272F2FR
Battery
Load Level
Approximate Back-Up Time (Minutes)
50%
14:30
100%
4:20
Note: Run times in this table are approximate . They are based upon new, fully charged standard battery modules at a temperature of
25°C (77°F) with 100% resistive UPS loading. Run times listed above can vary due to manufacturing variances of the individual
!
• Call SolaHD Technical Support for further instructions.
• Do not mount the UPS in upside down orientation.
10.2 Storage
Ambient temperature range is -15 °C to +60 °C (5 °F to 140 °F). It is recommended to charge the UPS
for at least 8 hours then store the UPS covered and upright in a cool, dry location. Remove
accessories and disconnect cables connected to the UPS to avoid unnecessary draining of the battery.
Extended Storage
During extended storage in environments where the ambient temperature is:
-15 °C to +30 °C (+5 °F to +86 °F), charge the UPS battery every six months.
During extended storage in environments where the ambient temperature is:
+30 °C to +45 °C (+86 °F to +113 °F), charge the UPS battery every three months.
16 |
P a g e
CERTIFICATIONS
UL 1778, 5th Ed./CSA 107.3 overvoltage category II, pollution degree 2.
UPS evaluated for use in UL 508 industrial control applications overvoltage
category III, pollution degree 3 with no output derating
UL121201/CSA 213 Class I, Division 2 Groups A B C D T4
ATEX – EN IEC 60079-0, EN 60079-7, EN 60079-15 II 3 G
UL 20 ATEX 2442X Ex ec nC IIC T4 Gc
LVD EN 62040-1
ODVA Compliant
FCC Part 15, Subpart B, Class A Level 4
EMC Directive – EN62040-2; EN55032; EN 55011, EN 55024, EN 61000-6-1,
EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61326-1, EN61000-3-2,
EN 61000-3-3, IEC/EN 61000-4 Series (Level 4, Criterion A),
IEC/EN 61000-4-3 (Level 3, Criterion A)
SDU 500B, SDU 500B-5
500/300
Yuasa REW7-12FR
14:30
4:20
Table 2. Battery Back-Up Time Chart
SDU 850B, SDU 850B-5
850/510
CSB XTV1285F2FR
Approximate Back-Up Time (Minutes)
7:00
1:30
Yuasa REW45-12FR
7:00
1:30
batteries.