Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages resulting from the use or application of the product. Reproduction of the contents of this manual, in whole or in part, without written permission from ProSoft Technology is prohibited.
Page 3
32K maximum HTML page size (previously limited to 16K) To upgrade a previously purchased Series C model: Contact your ProSoft Technology distributor to order the upgrade and obtain a Returned Merchandise Authorization (RMA) to return the unit to ProSoft Technology.
Verify Acyclic Communication (Mailbox Messaging) ..........31 Next Steps Support, Service & Warranty How to Contact Us: Technical Support ..............37 Return Material Authorization (RMA) Policies and Conditions........ 38 LIMITED WARRANTY..................... 39 Index ProSoft Technology, Inc. Page 5 of 45 November 20, 2008...
Page 6
Contents 5604-RIO-PDPMV1 ♦ ProLinx Standalone Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway Page 6 of 45 ProSoft Technology, Inc. November 20, 2008...
ProLinx 5604-RIO-PDPMV1 device. Important: This Setup Guide shows you how to set up a simple RIO to PDPMV1 network between a PLC5 processor and a ProLinx 5604-RIO-PDPMV1 module. This guide should be used as a starting point only. In all likelihood, the requirements of your particular application will involve additional configuration and development.
Whether you are configuring your modules on the fly or just reading through to understand how to use the sample application, there are steps that you must perform even if you are not yet configuring any modules to suit your own application. Page 8 of 45 ProSoft Technology, Inc. November 20, 2008...
Install ProSoft Configuration Builder (PCB) ProSoft Configuration Builder helps you configure the module for your application. Insert the ProLinx Solutions CD into the CD-ROM drive on your PC. The ProLinx Solutions splash page appears: ProSoft Technology, Inc. Page 9 of 45 November 20, 2008...
Copy the Sample Application Files From the ProLinx Solutions splash screen, click Product Documentation. Choose Samples / RIO-PDPMV1. Copy the RIO-PDPMV1.ppf and RIOPDPMV1_SAMPLE.RSP files to a location on your PC. Page 10 of 45 ProSoft Technology, Inc. November 20, 2008...
Important: Take care not to overwrite existing data files in your application with data files in the sample application. Rename either the source or the destination data files, and then search and replace references in the ladder for instances of any renamed files. ProSoft Technology, Inc. Page 11 of 45 November 20, 2008...
Connect the right-angle connector end of the cable to your controller at the communications port. Connect the straight connector end of the cable to the serial port on your computer. Page 12 of 45 ProSoft Technology, Inc. November 20, 2008...
Click the Download button to transfer the sample program to the processor. When prompted, choose Computer to PLC RSLogix will compile the program and transfer it to the processor. This process may take a few minutes. ProSoft Technology, Inc. Page 13 of 45 November 20, 2008...
Page 14
Note: If the list of configured drivers is blank, you must first choose and configure a driver from the Available Driver Types list. The recommended driver type to choose for serial communication with the processor is "RS-232 DF1 Devices". Page 14 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 15
If you are still unable to auto-configure the port, refer to your RSLinx documentation for further troubleshooting steps. ProSoft Technology, Inc. Page 15 of 45 November 20, 2008...
Page 16
5604-RIO-PDPMV1 ♦ ProLinx Standalone About the Sample PLC5 Program Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway Page 16 of 45 ProSoft Technology, Inc. November 20, 2008...
5604-RIO-PDPMV1.PPF. Start PCB. Select File / Open. Navigate to the location where you copied the 5604-RIO-PDPMV1.PPF file and select this file. Expand the 5604-RIO-PDPMV1 module selection. ProSoft Technology, Inc. Page 17 of 45 November 20, 2008...
Master and a single ProLinx PROFIBUS DP Slave (PDPS) device. To view the sample PROFIBUS network configuration, double-click the icon. This action opens the PDPMV1 PROFIBUS Master Setup dialog box. Page 18 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 19
When you have finished examining the sample PROFIBUS network configuration, close the ProSoft Configuration Builder for PROFIBUS window. Click OK to close the PDPMV1 PROFIBUS Master Setup dialog box and return to ProSoft Configuration Builder. ProSoft Technology, Inc. Page 19 of 45 November 20, 2008...
Page 20
Refer to the PDPMV1 Driver Manual, located on the ProLinx Solutions CD, for information on how to configure these settings for your own application. After making changes, be sure to save your changes before moving on to the next step. Page 20 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 21
4.1.3 Ethernet Configuration The Ethernet Configuration section is optional, and is required only if you will be using ProSoft Technology's PROFIBUS comDTM. PROFIBUS comDTM allows configuration tools, instruments and communication devices on a field network to recognize and use the module's capabilities. Refer to the PDPMV1 Driver Manual for more information on PROFIBUS comDTM.
Page 22
This section does not require any editing for the sample application. Refer to the ProLinx Reference Guide, located on the ProLinx Solutions CD, for information on setting up data mapping for your application. Page 22 of 45 ProSoft Technology, Inc. November 20, 2008...
This section of the configuration associates the internal database registers with the PLC input and output images. Refer to the RIO driver manual for information on each of these parameters. ProSoft Technology, Inc. Page 23 of 45 November 20, 2008...
Apply power to the module if you have not already done so. Choose File / Save As… and save the .PPF file to a location on your hard drive. Right-click on 5604-RIO-PDPMV1 and select Download from PC to Device. Page 24 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 25
OK. The module will perform a platform check to read and load its new settings. When the platform check is complete, the status bar in ProSoft Configuration Builder will be updated with the message "Module Running". ProSoft Technology, Inc. Page 25 of 45 November 20, 2008...
Page 26
5604-RIO-PDPMV1 ♦ ProLinx Standalone Configure the Remote I/O Adapter Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway Page 26 of 45 ProSoft Technology, Inc. November 20, 2008...
ProSoft Configuration Builder to perform these tests. Connect to the Debug Port on the 5604-RIO-PDPMV1 module. Ensure that power is applied to the module. Right-click on 5604-RIO-PDPMV1 and select Diagnostics. ProSoft Technology, Inc. Page 27 of 45 November 20, 2008...
Verify Cyclic Communication (PROFIBUS Slave I/O) For this example, open the sample program in RSLogix 5, and then double- click to open data file N16. Enter the values in this illustration at offset N16:0. Page 28 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 29
1000. The following illustration shows the module's database in Decimal format. Press [H] to view the same values in Hexadecimal format. ProSoft Technology, Inc. Page 29 of 45 November 20, 2008...
Page 30
Observe that the values in the first line of the Data from Master pane match the values in the hexadecimal database display in the ProSoft Configuration Builder Diagnostics window in Step 2. Page 30 of 45 ProSoft Technology, Inc. November 20, 2008...
For this example, we will trigger the Get Live List mailbox command. In ProSoft Configuration Builder, double-click on the icon. This action opens the Edit Profibus Master Commands dialog box, populated with one command. ProSoft Technology, Inc. Page 31 of 45 November 20, 2008...
Page 32
This register corresponds to register N16:806 in the PLC5 processor. To trigger the command, change the value of register N16:806 from 0 to 1. This value is immediately transmitted from the PLC5 processor to the 5604-RIO- PDPMV1 module. Page 32 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 33
Slave address 0 is offline. The Master is at address 1. The second register (0004) indicates that Slave address 2 is offline and Slave address 3 is online. The third register (0000) indicates that slaves 4 and 5 are online. ProSoft Technology, Inc. Page 33 of 45 November 20, 2008...
Page 34
5604-RIO-PDPMV1 ♦ ProLinx Standalone Verify Data Exchange Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway Page 34 of 45 ProSoft Technology, Inc. November 20, 2008...
PROFIBUS DP-V1 Master protocol, refer to the PDPMV1 Driver Manual. For technical support and warranty information for your ProLinx module, refer to Support, Service and Warranty (page 37) in this manual. For more information on ProSoft Technology products and services, please visit http://www.prosoft-technology.com. ProSoft Technology, Inc.
Page 36
5604-RIO-PDPMV1 ♦ ProLinx Standalone Next Steps Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway Page 36 of 45 ProSoft Technology, Inc. November 20, 2008...
How to Contact Us: Technical Support..........37 Return Material Authorization (RMA) Policies and Conditions....38 LIMITED WARRANTY................39 ProSoft Technology, Inc. (ProSoft) is committed to providing the most efficient and effective support possible. Before calling, please gather the following information to assist in expediting this process:...
If no defect is found, Customer will be charged the equivalent of $100 USD, plus freight charges, duties and taxes as applicable. A new purchase order will be required. Page 38 of 45 ProSoft Technology, Inc. November 20, 2008...
(collectively, the "Terms") of this Limited Warranty. All sales of software or other intellectual property are, in addition, subject to any license agreement accompanying such software or other intellectual property. ProSoft Technology, Inc. Page 39 of 45 November 20, 2008...
Page 40
Product such as, but not limited to, exposure to extremes of temperature or humidity, power failure or power surges; or (viii) disasters such as fire, flood, earthquake, wind and lightning. Page 40 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 41
Customer is granted no right or license to use any software or other intellectual property in any manner or for any purpose not expressly permitted by any license agreement accompanying such software or other intellectual property. ProSoft Technology, Inc. Page 41 of 45 November 20, 2008...
Page 42
This Warranty gives you specific legal rights, and you may also have other rights which vary from place to place. 8.3.7 Time Limit for Bringing Suit Any action for breach of warranty must be commenced within 39 months following shipment of the Product. Page 42 of 45 ProSoft Technology, Inc. November 20, 2008...
Page 43
Warranty shall remain in full force and effect. Any cause of action with respect to the Product or Services must be instituted in a court of competent jurisdiction in the State of California. ProSoft Technology, Inc. Page 43 of 45 November 20, 2008...
Page 44
5604-RIO-PDPMV1 ♦ ProLinx Standalone Support, Service & Warranty Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway Page 44 of 45 ProSoft Technology, Inc. November 20, 2008...