IBA ibaPADU-4-AI-U Manual

Input module with 4 fast analog voltage inputs

Advertisement

Quick Links

ibaPADU-4-AI-U
Manual
ibaPADU-4-AI-U
Input module with 4 fast analog voltage inputs
Manual
Issue 1.1
Issue 1.1
1

Advertisement

Table of Contents
loading

Summary of Contents for IBA ibaPADU-4-AI-U

  • Page 1 Manual ibaPADU-4-AI-U Input module with 4 fast analog voltage inputs Manual Issue 1.1 Issue 1.1...
  • Page 2 However, the information in this publication is updated regularly. Required cor- rections are contained in the following regulations or can be downloaded on the Internet. The current version is available for download on our web site http://www.iba-ag.com. Protection note Windows®...
  • Page 3: Table Of Contents

    Point-to-point connection ................16 Ring topology ....................16 Configuration in ibaPDA ................17 First steps ....................17 ibaPADU-4-AI-U – “General“ tab ..............18 ibaPADU-4-AI-U – “Analog” tab ..............19 PADU-4-AI-U – “Diagnostics“ tab ..............20 Technical Data ....................22 10.1 Main data ....................
  • Page 4 Manual ibaPADU-4-AI-U Support and contact ..................25 Issue 1.1...
  • Page 5: About This Manual

    Manual About this manual This manual describes the construction, the use and the operation of the device ibaPADU-4-AI-U. Target group This manual addresses in particular the qualified professionals who are familiar with han- dling electrical and electronic modules as well as communication and measurement tech- nology.
  • Page 6: Used Symbols

    Manual ibaPADU-4-AI-U Used symbols If safety instructions or other notes are used in this manual, they mean: The non-observance of this safety information may result in an imminent risk of death or severe injury:  By an electric shock!  Due to the improper handling of software products which are coupled to...
  • Page 7: Introduction

    Manual Introduction The ibaPADU-4-AI-U compact device has been developed for capturing and recording fast analog signals. The sampling rate can be adjusted freely up to 100 kHz max. The device offers 4 electrically isolated voltage inputs. The measuring ranges of these inputs are adjustable in several stages from ±250 mV up to ±24 V.
  • Page 8: Scope Of Delivery

    Scope of delivery After unpacking check the completeness and intactness of the delivery. The scope of delivery includes:  ibaPADU-4-AI-U device  2-pin connector for power supply  12-pin connector for connecting the analog signals  Manual Safety instructions Designated use The device is electrical equipment.
  • Page 9: System Requirements

    Manual System requirements Hardware For operation  Power supply 24 V DC ±10% For parametrization of the device and for measuring:  PC with the following minimum equipment  One free PCI, PCI Express or ExpressCard slot (Notebook).  At least 512 MB RAM ...
  • Page 10: Mounting And Dismounting

    Manual ibaPADU-4-AI-U Mounting and dismounting Mounting 1. Locate the DIN rail mounting clip on the rear side of the device. Slowly push down and in so that the bottom part of the mounting clips snaps onto the bottom part of the rail and firmly fixes the device to the DIN rail.
  • Page 11: Device Description

    Manual Device description Device view (1) Operating state display (2) FO input (RX) X11 (3) FO output (TX) X10 (4) Status LEDs of analog channels (5) Rotary switch S1 (6) Power supply terminal X14 (7) Analog inputs X1 Figure 1: Front view...
  • Page 12: Indicator Elements

    32Mbit Flex signal detected L4: (red) device functioning properly blinking failure, internal applications do not run device is defect, contact the iba support Status of analog inputs LED per channel Status Description (approx. values) voltage < ±1% of the selected input range L26 …...
  • Page 13: Connections

    The fiber optic ports and transmitters are the physical base for a simple send-and-receive connection to an ibaFOB card. The ports are designed for cables with 62.5/125 µm multi- mode fibers and ST couplings which are available at iba too. 7.3.2 Power supply The device requires an external DC 24 V ±10% power supply (unregulated) and should...
  • Page 14 Manual ibaPADU-4-AI-U 7.3.3.2 Connection diagram / pin assignment Here, you can connect 4 input signals (0…3), each bipolar and electrically isolated. Each channel is connected by means of two-wire connection. Figure 4: Connection diagram Pin assignment X1: Pin Connection Analog input 00 + Analog input 00 −...
  • Page 15: Operating Elements

    Manual Operating elements 7.4.1 Rotary switch S1 Up to 15 devices can be connected in a ring topology with 32Mbit Flex. The address of the device in a ring is set by the S1 rotary switch. Device number within the...
  • Page 16: System Integration

    Up to 15 devices can be connected to a ring. Configuration and process data are trans- mitted in the ring. Other 32Mbit Flex-enabled iba devices can be integrated into the ring as well. The de- vices in the ring are addressed via the S1 rotary switch.
  • Page 17: Configuration In Ibapda

    1. Start the ibaPDA client and open the I/O manager 2. Choose the correct ibaFOB-D input card in the signal tree (on the left hand side) and mark the link ibaPADU-4-AI-U is connected to. Right-click on the link and choose “Autodetect”.
  • Page 18: Ibapadu-4-Ai-U - "General" Tab

    Manual ibaPADU-4-AI-U ibaPADU-4-AI-U – “General“ tab Figure 7: ibaPADU-4-AI-U – ”General“ tab Basic  Module type (information only) Indicates the type of the current module.  Locked A module can be locked to avoid unintentional or unauthorized changing of the module settings.
  • Page 19: Ibapadu-4-Ai-U - "Analog" Tab

    By means of this command, you can read the configuration from the device. The changed settings become valid by clicking on <OK> or <Apply>. ibaPADU-4-AI-U – “Analog” tab Figure 8: ibaPADU-4-AI-U – ”Analog“ tab  Name Assign a meaningful name to each signal and you can enter additionally two com- ments when clicking on the symbol in the field “Name”.
  • Page 20: Padu-4-Ai-U - "Diagnostics" Tab

    Here, you find information about the hardware version, firmware version, FPGA version and the serial number of your device.  Write firmware Using this button you can install a firmware update. Select the update file ”padu4_v[xx.yy.zzz].iba “ in the browser and start the update with <OK>. Issue 1.1...
  • Page 21 Manual Important note The update may take approx. 30 s and must not be interrupted. After an update the de- vice will be automatically rebooted.  Reset to factory defaults Using this button all settings are reset to factory defaults after having confirmed the following request with <Yes>.
  • Page 22: Technical Data

    Manual ibaPADU-4-AI-U Technical Data 10.1 Main data Name ibaPADU-4-AI-U Description Input module with 4 analog voltage inputs Order no. 10.121000 Analog inputs Number Design Galvanically isolated, single ended Resolution 16 Bit Filter permanent R/C low-pass, 1 order, 72 kHz in addition...
  • Page 23 Weight / incl. box and documentation 1.54 lbs (0.7 kg) / 2.42 lbs (1.1 kg) Supplier's Declaration of Conformity 47 CFR § 2.1077 Compliance Information Unique Identifier: 10.121000 ibaPADU-4-AI-U Responsible Party - U.S. Contact Information iba America, LLC 370 Winkler Drive, Suite C Alpharetta, Georgia 30004 (770) 886-2318-102 www.iba-america.com FCC Compliance Statement This device complies with Part 15 of the FCC Rules.
  • Page 24: Dimension Sheet

    Manual ibaPADU-4-AI-U 10.2 Dimension sheet (Dimensions in mm) Figure 10: Dimensions ibaPADU-4-AI-U (Dimensions in mm) Figure 11: Dimensions ibaPADU-4-AI-U with cable Issue 1.1...
  • Page 25 Mailing address iba AG Postbox 1828 D-90708 Fuerth Germany Delivery address iba AG Gebhardtstrasse 10 D-90762 Fuerth Germany Regional and Worldwide For contact data of your regional iba office or representative please refer to our web site www.iba-ag.com. Issue 1.1...