4.5 Extension Elements

The MonsterFans fans are delivered ex-works with a hanging element of standard 1m.
Optionally, we offer another 1 m and 2 m extension element and a connection piece to
connect two extension elements.
The max. length of these extension elements must not exceed 3 m consisting of max. 2
elements. Likewise, only one connection set may be used to connect two extension
elements. Otherwise the stability of the fan can be influenced.
Extension tube
1 m standard length
Article no: 19580230
Weight: 8 kg
Connecting piece for extension tubes incl. bolts & screws:
Article no. 19580239
Weight: 3 kg
4.6 Wire rope clamps & Thimbles
EN 13411-5:2009-02 stipulates the use of at least 3 wire rope clamps and thimbles for end
connections for steel wire ropes of nominal size 5 mm.
The first wire rope clamp should be attached directly to the thimble. The clamp should
always be attached to the loaded part of the rope.
The distance "e" between the wire rope clamps should be at least 1.5 "t" and not more than 3
"t", where "t" is the width of the clamp jaw.
When making the connection and before commissioning, the collar nuts should be tightened
to a torque of 2 Nm. The recommended tightening torque applies to wire rope clamps where
the contact surfaces and threads of the nuts have been lubricated.
After the first application of the load the tightening torque should be checked again and
corrected if necessary.
www.monsterfans.com
Optional Extension tube 1,5 m length
Article no 19580231
Weight: 12 kg
Optional Extension tube 2 m length
Article no 19580232
Weight: 16 kg