Busch-Jaeger 1091 U Operating Instructions Manual page 22

Co2-sensor
Table of Contents

Advertisement

For a set window control:
Fig. 18:
Window control: CO
exceeded
Fig. 19:
Window control: RH threshold value
exceeded
Exceeding of the threshold value:
If the set threshold value is exceeded, the control switches the window to open. The open
circuit is maintained for 3 minutes.
Dropping below the threshold value:
If the measured value drops below the threshold value by 10 ppm or 1% for the relative
humidity (RH), the control switches the window to close after the set switch-off delay. The
close circuit is maintained for 3 minutes.
Operating Instructions 2CKA001473B8822
threshold value
2
The entered CO
limit value has been
2
exceeded.
The window opens automatically.
The entered limit value for the
relative humidity (RH) has been
exceeded.
The window opens automatically.
Operation
│22