Midea MCA3U-18HRFNX-QRD0W Service Manual page 63

Hide thumbs Also See for MCA3U-18HRFNX-QRD0W:
Table of Contents

Advertisement

No.
Name
1
Power Supply
2
S
3
HEAT1
4
4-WAY
5
HEAT2
6
AC-FAN
7
TP T4 T3
8
TP T4 T3
9
PMV
10
DC-FAN
11
FAN_IPM
12
TESTPORT
13
EE_PORT
14
MCUPORT
W
15
V
U
16
COMP_IPM
17
CN9
18
CN32
Note: This section is for reference only. Please take practicality as standard.
CN#
CN3
Earth: connect to Ground
CN1
N_in: connect to N-line (208-230V AC input)
CN2
L_in: connect to L-line (208-230V AC input)
CN16
S: connect to indoor unit communication
CN17
connect to compressor heater, 208-230V AC when is ON
CN60
connect to 4 way valve, 208-230V AC when is ON.
CN15
connect to chassis heater, 208-230V AC when is ON
CN25
connect to AC fan
connect to pipe temp. sensor T3, ambient temp. sensor T4, exhaust
CN22
temp. sensor TP
connect to pipe temp. sensor T3, ambient temp. sensor T4, exhaust
CN21
temp. sensor TP
CN31
connect to Electric Expansion Valve
CN7
connect to DC fan
IPM 501
IPM for DC fan
CN6
used for testing
CN505
EEPROM programer port
CN507
connect to PC communication
CN28
connect to compressor
CN29
0V AC (standby)
CN30
10-200V AC (running)
IPM 301
IPM for compressor
CN9
connect to reactor
CN32
connect to reactor
Meaning