Huawei UPS2000-G-15KRTL Quick Manual page 36

Hide thumbs Also See for UPS2000-G-15KRTL:

Advertisement

Alarm
Alarm ID-
Name
Cause ID
Batt.
0026-01
undervolt.
Rectifier
0040-04
fault
Internal
0042-10
fault
Fan fault
0043-01
Alarm
Clearance
Severity
Mode
Minor
Automatic
Critical
Manual/Po
wer-
off/Autom
atic
Critical
Automatic
Critical
Automatic
Impact on
Handling Suggestion
the System
An alarm is
displayed,
and the
system may
shut down
due to EOD.
The UPS
Possible causes:
shuts down.
The UPS
transfers to
another
working
mode or
shuts down.
Measures:
If the inverter
Possible cause: The bypass
has not
input cable connection is
started,
inconsistent with the output
disable
system setting.
inverter
Measure: Ensure that the
startup.
bypass input cable connection
If the inverter
is consistent with the output
has started,
system setting.
the UPS can
work in
inverter
mode
properly, but
the UPS
cannot
transfer to
bypass mode.
This alarm
Possible cause: The fan is
does not
abnormal.
affect the
Measure: Clean up foreign
UPS or the
objects around the fan. If the
power supply.
alarm persists, contact Huawei
technical support.
36
Possible cause: The mains is
abnormal, and the batteries
are overdischarged.
Measure: Connect to the
mains supply in non-battery
test state.
The mains has experienced
a transient high voltage.
The output carries special
loads such as inductive and
rectification loads.
The output carries
transformer loads but the
transformer mode is not
enabled.
The hardware is damaged.
Rectify the fault and power
on the UPS again.
Check that the loads are
supported by the UPS.
Enable the transformer
mode.
Contact Huawei technical
support.