Alarm
Alarm ID-
Name
Cause ID
Mains
0004-01
phase
reverse
BPS phase
0011-01
reverse
Batt.
0025-01
overvolt.
Alarm
Clearance
Severity
Mode
Minor
Automatic
Minor
Automatic
Minor
Automatic
Impact on the
Handling Suggestion
System
The rectifier
Possible cause: The mains input
transfers to
three-phase sequence is
battery mode,
incorrect.
which does
Measure: Check that mains
not affect the
input power cables are correctly
system power
connected.
supply.
If no battery is
installed, the
UPS shuts
down.
The UPS
transfers to
another
working mode
or shuts
down.
If the inverter
Possible cause: The bypass input
has not
three-phase sequence is
started, the
incorrect.
output keeps
Measure: Check that bypass
disconnected
input power cables are correctly
and the
connected.
inverter is not
allowed to
start.
If the inverter
has started,
the UPS can
work in
inverter mode
properly, but
the UPS
cannot
transfer to
bypass mode.
Possible causes:
An alarm is
displayed, and
the battery
service life may
be shortened.
Measures:
35
The configured number of
batteries is less than the
actual number.
The battery voltage reaches
the alarm threshold due to
continuous charge.
Check battery parameter
settings.
Wait for 2 minutes in battery
charging state. Check
whether the alarm is cleared.