Alarm
Alarm ID-
Name
Cause ID
Mains
0004-01
phase
reverse
BPS phase
0011-01
reverse
Batt.
0025-01
overvolt.
Alarm
Clearance
Severity
Mode
Minor
Automatic
Minor
Automatic
Minor
Automatic
Impact on the
Handling Suggestion
System
•
The rectifier
Possible cause: The mains input
transfers to
three-phase sequence is
battery mode,
incorrect.
which does
Measure: Check that mains
not affect the
input power cables are correctly
system power
connected.
supply.
•
If no battery is
installed, the
UPS shuts
down.
•
The UPS
transfers to
another
working mode
or shuts
down.
•
If the inverter
Possible cause: The bypass input
has not
three-phase sequence is
started, the
incorrect.
output keeps
Measure: Check that bypass
disconnected
input power cables are correctly
and the
connected.
inverter is not
allowed to
start.
•
If the inverter
has started,
the UPS can
work in
inverter mode
properly, but
the UPS
cannot
transfer to
bypass mode.
Possible causes:
An alarm is
•
displayed, and
the battery
•
service life may
be shortened.
Measures:
•
•
35
The configured number of
batteries is less than the
actual number.
The battery voltage reaches
the alarm threshold due to
continuous charge.
Check battery parameter
settings.
Wait for 2 minutes in battery
charging state. Check
whether the alarm is cleared.