APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP
5 Ton Heat Pump
Standard Static Drive
Models: DRH0601D and DRH0603D
Down Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM BHP
TAP
(ESP),
IN WC
0.2
1299
614 0.16
0.4
1209
674 0.17
T1
0.6
1082
755 0.19
0.8
933
836 0.21
1.0
835
889 0.23
0.2
1967
862 0.62
0.4
1896
951 0.69
T2
0.6
1849 1022 0.74
0.8
1786
948 0.69
1.0
1710
996 0.72
0.2
1967
862 0.62
0.4
1896
951 0.69
T3
0.6
1849 1022 0.74
0.8
1786
948 0.69
1.0
1710
996 0.72
0.2
2189
902 0.81
0.4
2119
943 0.84
T4
0.6
2059
979 0.88
0.8
2012 1009 0.90
1.0
1969 1048 0.94
0.2
2254
923 0.88
0.4
2178
964 0.92
T5
0.6
2127
997 0.95
0.8
2078 1029 0.98
1.0
2026 1060 1.01
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
Horizontal Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM BHP
TAP
(ESP),
IN WC
0.2
1326
653 0.22
0.4
1234
717 0.24
T1
0.6
1104
803 0.27
0.8
952
890 0.30
1.0
852
946 0.32
0.2
2007
885 0.64
0.4
1935
931 0.67
T2
0.6
1887
969 0.70
0.8
1822 1009 0.73
1.0
1745 1060 0.77
0.2
2007
885 0.64
0.4
1935
931 0.67
T3
0.6
1887
969 0.70
0.8
1822 1009 0.73
1.0
1745 1060 0.77
0.2
2234
960 0.86
0.4
2162 1003 0.90
T4
0.6
2101 1042 0.93
0.8
2053 1073 0.96
1.0
2009 1115 1.00
0.2
2300
982 0.93
0.4
2222 1025 0.98
T5
0.6
2170 1061 1.01
0.8
2120 1095 1.04
1.0
2067 1128 1.07
5 Ton Heat Pump
Standard Static Drive
Models: DRH0604D and DRH0607D
Down Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM BHP
TAP
(ESP),
IN WC
0.2
1130 498 0.11
0.4
1046 551 0.12
T1
0.6
886
647 0.15
0.8
737
727 0.16
1.0
585
803 0.18
0.2
1964 806 0.52
0.4
1877 857 0.55
T2
0.6
1786 909 0.58
0.8
1711 970 0.62
1.0
1613 1028 0.66
0.2
1964 806 0.52
0.4
1877 857 0.55
T3
0.6
1786 909 0.58
0.8
1711 970 0.62
1.0
1613 1028 0.66
0.2
2071 842 0.58
0.4
1987 888 0.61
T4
0.6
1903 937 0.65
0.8
1838 995 0.69
1.0
1762 1041 0.72
0.2
2173 873 0.64
0.4
2095 921 0.68
T5
0.6
2009 967 0.71
0.8
1933 1015 0.75
1.0
1867 1062 0.78
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
27
Horizontal Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM BHP
TAP
(ESP),
IN WC
0.2
1154 529 0.12
0.4
1068 585 0.13
T1
0.6
904
687 0.16
0.8
752
772 0.17
1.0
597
853 0.19
0.2
2004 856 0.55
0.4
1916 911 0.59
T2
0.6
1823 966 0.62
0.8
1746 1031 0.66
1.0
1646 1093 0.70
0.2
2004 856 0.55
0.4
1916 911 0.59
T3
0.6
1823 966 0.62
0.8
1746 1031 0.66
1.0
1646 1093 0.70
0.2
2114 894 0.62
0.4
2028 944 0.65
T4
0.6
1941 996 0.69
0.8
1875 1057 0.73
1.0
1798 1106 0.76
0.2
2217 928 0.68
0.4
2138 979 0.72
T5
0.6
2050 1027 0.76
0.8
1973 1079 0.80
1905 1129 0.83
1.0