Daikin DRC036 Installation Instructions Manual page 12

Packaged air conditioner and heat pump unit 3-6 ton
Hide thumbs Also See for DRC036:
Table of Contents

Advertisement

GR (FAN)
Move YELLOW (YL) wire from TB1-T1 to T2 or T3 to change blower speed during cooling stage 1 operation.
* Move YELLOW (YL) wire from TB1-T1 to T2 or T3 to change blower speed during cooling stage 1 operation. (Do not
* Move YELLOW (YL) wire from TB1-T1 to T2 or T3 to change blower speed during cooling stage 1 operation. (Do not
(Do not move wires YL and PU to the same taps)
move wire YL and PU to the same taps)
move YL and PU on the same taps)
Move WHITE (WH) wire from TB1-T2 to T3 to change blower speed during heating stage 1 operation.
* Move WHITE (WH) wire from TB1-T2 to T3 to change blower speed during heating stage 1 operation. (Do not move
* Move WHITE (WH) wire from TB1-T2 to T3 to change blower speed during heating stage 1 operation. (Do not move
(Do not move wires WH and BR to the same taps)
WH and BR on the same taps)
wire WH and BR to the same taps)
Move PURPLE (PU) wire from TB1-T3 to T4 or T5 to change blower speed during cooling stage 2 operation.
* Move PURPLE (PU) wire from TB1-T3 to T4 or T5 to change blower speed during cooling stage 2 operation. (Do not
* Move PURPLE (PU) wire from TB1-T3 to T4 or T5 to change blower speed during cooling stage 2 operation. (Do not
(Do not move wires YL and PU to the same taps)
move wire YL and PU to the same taps)
move YL and PU on the same taps)
Move BROWN (BR) wire from TB1-T3 to T4 or T5 to change blower speed during heating stage 2 operation.
(Do not move wires WH and BR to the same taps)
* Move BROWN (BR) wire from TB1-T3 to T4 or T5 to change blower speed during heating stage 2 operation. (Do not
move wire YL and PU to the same taps)
GR (FAN)
Energized during Heat Mode
** TB1-DH is energized when the unit is in heat
mode. When TB1-DH is energized, the blower motor
operates at a new group of programmed speeds,
T6-T10, in place of T1-T5.
Move YELLOW (YL) wire from TB1-T1 to T2 or T3 to change blower speed during cooling stage 1 operation.
(Do not move wires YL and PU to the same taps)
Move WHITE (WH) wire from TB1-T6 to T7 to change blower speed during heating stage 1 operation.
(Do not move wires WH and BR to the same taps)
Move PURPLE (PU) wire from TB1-T3 to T4 or T5 to change blower speed during cooling stage 2 operation.
(Do not move wires YL and PU to the same taps)
Move BROWN (BR) wire from TB1-T8 to T9 or T10 to change blower speed during heating stage 2 operation.
(Do not move wires WH and BR to the same taps)
C/DRH
DRC/DRH Model Wiring (Hi Static)
(Standard Static)
12
BR (Heating Stage 2)
PU (Cooling Stage 2)
WH (Heating Stage 1)
YL (Cooling Stage 1)
BR (Heating Stage 2)
PU (Cooling Stage 2)
WH (Heating Stage 1)
YL
(Cooling Stage 1)