APPENDIX A BLOWER PERFORMANCE TABLES - AC
5 Ton Cooler
Standard Static Drive
Models: DRC0601D and DRC0603D
Down Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM BHP
TAP
(ESP),
IN WC
0.2
1111 557 0.14
0.4
987 639 0.16
T1
0.6
816 734 0.19
0.8
714 795 0.20
1.0
589 859 0.22
0.2
2079 886 0.72
0.4
2010 929 0.75
T2
0.6
1958 964 0.78
0.8
1919 994 0.80
1.0
1839 1033 0.84
0.2
1731 761 0.43
0.4
1675 805 0.46
T3
0.6
1607 847 0.48
0.8
1526 898 0.51
1.0
1429 962 0.55
0.2
2143 886 0.76
0.4
2064 929 0.80
T4
0.6
2010 964 0.83
0.8
1966 994 0.85
1.0
1903 1033 0.89
0.2
2254 923 0.88
0.4
2178 964 0.92
T5
0.6
2127 997 0.95
0.8
2078 1029 0.98
1.0
2026 1060 1.01
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
Horizontal Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM BHP
TAP
(ESP),
IN WC
0.2
1134 592 0.15
0.4
1007 680 0.17
T1
0.6
832
781 0.20
0.8
729
846 0.22
1.0
602
913 0.23
0.2
2121 942 0.76
0.4
2051 989 0.80
T2
0.6
1998 1026 0.83
0.8
1958 1057 0.86
1.0
1877 1099 0.89
0.2
1766 809 0.46
0.4
1709 856 0.49
T3
0.6
1640 901 0.51
0.8
1557 956 0.55
1.0
1458 1023 0.58
0.2
2187 942 0.81
0.4
2106 989 0.85
T4
0.6
2051 1026 0.88
0.8
2006 1057 0.91
1.0
1942 1099 0.94
0.2
2300 982 0.93
0.4
2222 1025 0.98
T5
0.6
2170 1061 1.01
0.8
2120 1095 1.04
1.0
2067 1128 1.07
Standard Static Drive
Models:
DRC0604D and DRC0607D
Down Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM
TAP
(ESP),
IN WC
0.2
1030 579 0.13
0.4
879
671 0.15
T1
0.6
700
765 0.17
0.8
538
853 0.19
1.0
461
847 0.19
0.2
1963 872 0.56
0.4
1861 927 0.60
T2
0.6
1775 972 0.62
0.8
1688 1021 0.66
1.0
1584 1080 0.69
0.2
1804 820 0.46
0.4
1695 879 0.49
T3
0.6
1610 931 0.52
0.8
1516 988 0.55
1.0
1417 1053 0.59
0.2
2037 897 0.62
0.4
1935 951 0.66
T4
0.6
1847 997 0.69
0.8
1768 1039 0.72
1.0
1665 1093 0.75
0.2
2110 921 0.68
0.4
2010 974 0.72
T5
0.6
1912 1024 0.76
0.8
1841 1060 0.78
1.0
1749 1108 0.82
Shaded area indicates air flow below 1500 SCFM (300 SCFM/ton) that
is not recommended for High Stage cooling or heating
19
5 Ton Cooler
Horizontal Flow
EXTERNAL
STATIC
SPEED
BHP
PRESSURE
SCFM RPM
TAP
(ESP),
IN WC
0.2
1063 560 0.13
0.4
936
T1
0.6
770
0.8
614
1.0
471
0.2
1998 818 0.53
0.4
1898 878 0.56
T2
0.6
1809 937 0.60
0.8
1715 992 0.64
1.0
1667 1036 0.67
0.2
1846 771 0.43
0.4
1744 832 0.47
T3
0.6
1643 897 0.50
0.8
1585 944 0.53
1.0
1480 1010 0.56
0.2
2073 839 0.58
0.4
1977 896 0.62
T4
0.6
1883 952 0.66
0.8
1794 1006 0.69
1.0
1747 1049 0.72
0.2
2141 856 0.63
0.4
2052 912 0.67
T5
0.6
1961 969 0.71
0.8
1870 1023 0.75
1.0
1794 1070 0.79
BHP
652 0.15
750 0.17
824 0.19
901 0.20