APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP
6 Ton Heat Pump
Standard Static Drive
Models: DRH0723D, DRH0724D and DRH0727D
Down Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM RPM BHP
TAP
(ESP),
IN WC
0.2
1394
635 0.21
0.4
1265
711 0.24
T1
0.6
1127
805 0.27
0.8
983
885 0.29
1.0
855
952 0.32
0.2
2301
832 0.77
0.4
2229
882 0.82
T2
0.6
2156
929 0.86
0.8
2083
979 0.91
1.0
2011 1033 0.96
0.2
2226
892 0.69
0.4
2143
931 0.72
T3
0.6
2052
973 0.75
0.8
1950 1027 0.79
1.0
1861 1080 0.84
0.2
2301
903 0.84
0.4
2229
935 0.87
T4
0.6
2156
987 0.92
0.8
2083 1034 0.96
1.0
2011 1080 1.00
0.2
2435
972 0.93
0.4
2362 1007 0.96
T5
0.6
2293 1043 0.99
0.8
2209 1086 1.03
2124 1134 1.08
1.0
Shaded area indicates air flow below 1800 SCFM (300 SCFM/ton) that
is not recommended for High Stage cooling or heating
Horizontal Flow
EXTERNAL
STATIC
SPEED
PRESSURE
SCFM
RPM BHP
TAP
(ESP),
IN WC
0.2
1382
642 0.21
0.4
1259
724 0.24
T1
0.6
1160
799 0.27
0.8
1016
879 0.29
1.0
899
948 0.32
0.2
2348
926 0.86
0.4
2274
973 0.90
T2
0.6
2200
1020 0.95
0.8
2126
1066 0.99
1.0
2052
1113 1.03
0.2
2211
885 0.68
0.4
2128
938 0.73
T3
0.6
2034
988 0.76
0.8
1950
1042 0.81
1.0
1859
1098 0.85
0.2
2348
926 0.86
0.4
2274
973 0.90
T4
0.6
2200
1020 0.95
0.8
2126
1066 0.99
1.0
2052
1113 1.03
0.2
2404
961 0.91
0.4
2347
995 0.95
T5
0.6
2273
1050 1.00
0.8
2193
1100 1.05
2111
1149 1.09