MAXI 1100, 2000 Compact Air Handling Unit Operation and maintenance instructions Corrigo ver. no. 3.0-1-03...
Page 2
2. Alarm LED 7a. Yellow cable 3. Write enable LED 7b. Orange cable 4. OK button 7c. Red cable 5. Clearing button 7d. Brown cable 6. Mounting holes 7e. Black cable _____________________________________________________________________________________________________ Maxi 1100-2000 Operation- and maintenance instructions 204414 Systemair AB...
Page 3
Fig 3 Description MAXI 1100 Supply air fan with inspection hole for inspection of Contactor, exhaust fan speed normal (K3) rotation direction Exhaust air fan with inspection hole for checking of Contactor, supply fan speed reduced (K2) rotation direction Extract filter, G3...
Page 4
Fuse, EL- heating battery (EL units) Sensor, Extract air temperature Contactor, EL- heating battery (K5) (EL units) Sensor, Outdoor air temperature Contactor, HW pump (K7) (HW units) Sensor, Defrosting temperature _____________________________________________________________________________________________________ Maxi 1100-2000 Operation- and maintenance instructions 204414 Systemair AB...
Introduction Installation, operation and maintenance manual concerns air handling unit type MAXI, manufactured by Systemair AB. It consists of basic information and recommendations concerning the design, installation, start-up and operation, to ensure a proper fail-free operation of the unit. The key to proper and safe operating of the unit is to read this manual thoroughly, use the unit according to given guidelines and follow all safety requirements.
To pass a value without changing it, press RIGHT. To abort a change and return to the initial setting, press and hold the C-button until the cursor disappears. _____________________________________________________________________________________________________ Maxi 1100-2000 Operation- and maintenance instructions 204414 Systemair AB...
Switch on the supply voltage. Set present time and date, set the control temperature and program the week schedule. Do the necessary settings for extra functions if any. _____________________________________________________________________________________________________ Maxi 1100-2000 Operation- and maintenance instructions 204414 Systemair AB...
Maintenance of the MAXI should normally be carried out 3 – 4 times a year. Apart from general cleaning the following should be observed: NOTE! For the Maxi 1100 both the inspection doors are fastened to the unit casing by 8 toggle locks. The two inspection doors are connected between themselves with hinges. When the unit...
RESET (pos.24 in fig.3 and pos.23 in fig.4). Check if the extract filter must be changed. Check that the By-pass damper is closed. By-pass damper is standard in MAXI 1100 and accessory to MAXI 2000. Check if the fan thermo contact has tripped, shows as Malf. SAF or EAF in the control panel. If necessary, reset it (see page 6 Alarms).
Page 24
Systemair AB reserves the rights at any time, without prior notice, make changes and improvements to the contents of this manual. Systemair AB Industrivägen 3 SE-739 30 Skinnskatteberg Phone +46 222 440 00 Fax +46 222 440 99 www.systemair.com 204414 (24-05-2011)