3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS Installation and maintenance...
Page 2
Warning symbol for general danger to personnel. Warning symbol for electrical danger to personnel. Note: LEROY-SOMER reserves the right to modify the Copyright 2005: LEROY-SOMER characteristics of its products at any time in order to This document is the property of: incorporate the latest technological developments.
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS CONTENTS 1 - RECEIPT 5 - SPARE PARTS 1.1 - Standards and safety measures ....4 5.1 - First maintenance parts ......17 1.2 - Inspection ............4 5.2 - Technical support service ......
The machine name is defined according to various criteria, for - the recommendations of the example: LSA 47.2 M7 C6/4 - International Electrotechnical Commission • LSA: name used in the PARTNER range IEC 34-1, (EN 60034).
2.1 - Electrical characteristics - Steel frame - Cast iron end shields The LSA 47.2 alternator is a machine without sliprings or - Protected ball bearings, greased for life revolving armature brushes, wound as “2/3 pitch”, 6 or - Mounting arrangements:...
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS INSTALLATION 3 - INSTALLATION 3.1.3 - Location Ensure that the ambient temperature in the room where the 3.1 - Assembly alternator is placed cannot exceed 40°C for standard power ratings (for temperatures >...
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS INSTALLATION 3.3 - Terminal connection diagrams To modify the connection, change the position of the stator cables on the terminals. The winding code is specified on the nameplate.
Page 8
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS INSTALLATION 3.3.2 - Terminal connection: 6 wire (not possible with the R 250) Connection codes Voltage L.L Factory connection 50 Hz 60 Hz L1(U)
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS INSTALLATION Current transformer connection D connection D & A connection - PH 1 In/2 - Secondary 1 A In/2 (D conn.) - Secondary 1 A...
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS SERVICING - MAINTENANCE 4 - SERVICING - MAINTENANCE 4.2.4 - Electrical servicing Cleaning product for the windings 4.1 - Safety measures WARNING WARNING Do not use: trichlorethylene, perchlorethylene, Servicing or troubleshooting must be carried out trichloroethane or any alkaline products.
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS SERVICING - MAINTENANCE 4.3 - Fault detection If, when commissioned, the alternator does not work normally, the source of the malfunction must be identified.
Page 12
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS SERVICING - MAINTENANCE 4.5.1 - Checking the winding Assembly A: Connect a 12 V battery in series with a rheostat of approximately 50 ohms - 300 W and a diode on both exciter You can check the winding insulation by performing a high field wires (5+) and (6-).
If the diodes are faulty, During the warranty period, this operation should - Remove the surge suppressor (347). only be carried out in an LEROY-SOMER approved - Remove the 6 "H" nuts for mounting the diode bridges on the support.
Page 14
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS SERVICING - MAINTENANCE 78 36 Threaded rod Dowel Rotor WARNING WARNING NDE shield When dismantling the rotor involves changing parts or rewinding, the rotor must be rebalanced.
After operational testing, replace all access panels or covers. 4.7 - Installation and maintenance of the PMG For the LSA 47.2, the PMG reference is: PMG 2. 4.7.1 - Mechanical characteristics The components are: - a shaft adapter (to position the rotor on the alternator shaft).
All values are given to within ± 10% and may be changed without prior notification (for exact values, consult the test report). 4.8.1 - Average values for the LSA 47.2 Resistances at 20 °C (Ω) LSA 47.2 L/N stator...
INSTALLATION AND MAINTENANCE LEROY-SOMER 3742 en - 06.2007 / d LSA 47.2 - 4 POLES ALTERNATORS SPARE PARTS 5 - SPARE PARTS 5.3 - Accessories 5.3.1 - Space heater for use when stopped 5.1 - First maintenance parts The space heater must run as soon as the alternator stops. It Emergency repair kits are available as an option.