Connecting
7.10 Digital inputs/outputs
Using shielded cables
When using a shielded cable for the bidirectional inputs/outputs, the following options are
available for the shield connection:
1. Attach the cable shield to a grounded shielding bus immediately after the cable entry point
in the cabinet (strip the insulation off the cable for this purpose).
2. Continue routing the shielded cable as far as the module but do not make a connection to the
shield there.
Using a shield connection
1. Remove the fixing bracket of the shield connection.
2. Insert the cable and fasten the fixing bracket.
Figure 7-13
7.10.4

Technical data

Digital inputs on X122/X132
Table 7-29
Parameters
Voltage
Typical current consumption
Galvanic isolation
80
Fixing bracket of the shield connection
Torx screw M3/0.8 Nm
Shield support
Technical data of digital inputs X122/X132
Values
-3 V to +30 V DC
9 mA at 24 V DC (only with NCU 710.3B)
2.5 mA at 24 V DC (only with NCU 720.3B/ 730.3B)
Reference potential is terminal G1 or G2
Equipment Manual, 10/2020, 6FC5397-1EP40-6BA1
NCU 7x0.3B PN