System Requirements; Computer; Ul 294 Level Descriptions; Installation Instructions - Bosch Access Modular Controller 2 Installation Manual

Hide thumbs Also See for Access Modular Controller 2:
Table of Contents

Advertisement

Access Modular Controller 2
6.1

System requirements

6.1.1

Computer

Host system
For detailed information about the needed Operating system and Hardware, please refer to
the corresponding installation manual of the used Management system.
Notice!
i
Computers used for UL installations must be UL listed by the Information Technology
Equipment Group (ITE).
6.2

UL 294 level descriptions

The following UL 294 levels apply:
6.3

Installation instructions

This system is to be installed indoors within the protected or restricted area.
The UL evaluated configuration requires the following restrictions:
Bosch Security Systems B.V.
ACCESS CONTROL DESTRUCTIVE ATTACK LEVEL I - An access control product intended
for, but not limited to, a controlled area that is not required to meet the destructive
Attack Test.
ACCESS CONTROL LINE SECURITY LEVEL I - An access control product with no
communication line security.
ACCESS CONTROL ENDURANCE LEVEL IV - An access control product shall operate as
intended at rated voltage and current for 100,000 cycles of intended operation.
ACCESS CONTROL STANDBY POWER LEVEL II - An access control product for units
employing Model APS-PSU-60 Power Supply for 12 VDC and 24 VDC Mode. Level II
operates for 30 minutes.
A connected Host Management System to configure the AMC2 controller, manage card
user database, etc. After configuration is done, the AMC2 controller is still able to work
as intended, without any connection to the Host Management System. However, alarm
status of the system will not be reflected.
UL evaluated that the protection is set by the Access System Software as supplementary
monitoring equipment.
The enclosure AMC2-UL01 or AMC2-UL02 is necessary. The AMC2 Controller and
Extension devices must be installed in one of these enclosures.
The tamper contact of the AMC2 Controller must be connected to the tamper switch of
the enclosure.
In one enclosure: when using an AMC2 controller and an AMC2 extension board, if the
AMC2 Extension board is supplied via the extension interface, the AC fail, DC fail, and
BAT fail contacts must be shorted.
The door locks should be connected as fail safe (NFPA 101).
For host system connection, only the Ethernet (RJ45) port must be used. The RS-232 and
RS-485 host connections may not be used in UL installations.
The RS-485 slave connection may be used for connection to other AMC2 Extension
devices only. It may not be used for connection to readers or other accessories.
All units are to be powered by the Bosch APS-PSU-60 power supply for UL installations.
The power supply must be located in the same room as the connected AMC2 device.
Recommended maximum distance between power supply unit and AMC2 is 3 m (9.84 ft).
Installation manual
UL requirements | en
35
2021-04 | V04 | IM