Troubleshooting

11.2.2 Symptom: Cool/Heat cannot be changed over

11.2.3 Symptom: Fan operation is possible, but cooling and heating do not work

11.2.4 Symptom: The fan speed does not correspond to the setting

11.2.5 Symptom: The fan direction does not correspond to the setting

11.2.6 Symptom: White mist comes out of a unit (Indoor unit)

11.2.7 Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)

Installer and user reference guide
42
starts 5 minutes after it is turned ON again in case it was turned OFF just before.
The same starting delay occurs after the operation mode selector button was
used.
If "Under Centralized Control" is displayed on the user interface, pressing the
operation button causes the display to blink for a few seconds. The blinking
display indicates that the user interface cannot be used.
The system does not start immediately after the power supply is turned on. Wait
one minute until the micro computer is prepared for operation.
When the display shows
that this is a slave user interface.
When the cool/heat changeover remote control switch is installed and the
display shows
(change-over under centralized control), this is because cool/
heat changeover is controlled by the cool/ heat changeover remote control
switch. Ask your dealer where the remote control switch is installed.
Immediately after the power is turned on. The micro computer is getting ready to
operate and is performing a communication check with all indoor units. Please wait
12 minutes maximally until this process is finished.
The fan speed does not change even if the fan speed adjustment button is pressed.
During heating operation, when the room temperature reaches the set
temperature, the outdoor unit goes off and the indoor unit changes to whisper fan
speed. This is to prevent cold air blowing directly on occupants of the room. The
fan speed will not change even when another indoor unit is in heating operation, if
the button is pressed.
The fan direction does not correspond with the user interface display. The fan
direction does not swing. This is because the unit is being controlled by the micro
computer.
When humidity is high during cooling operation. If the interior of an indoor unit is
extremely contaminated, the temperature distribution inside a room becomes
uneven. It is necessary to clean the interior of the indoor unit. Ask your dealer for
details on cleaning the unit. This operation requires a qualified service person.
Immediately after the cooling operation stops and if the room temperature and
humidity are low. This is because warm refrigerant gas flows back into the indoor
unit and generates steam.
When the system is changed over to heating operation after defrost operation.
Moisture generated by defrost becomes steam and is exhausted.
(change-over under centralized control), it shows
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482277-1B – 2020.10