18.2.7 Using the stop valve and service port
To handle the stop valve
To open/close the stop valve
To handle the stop valve cover
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482277-1B – 2020.10
Take the following guidelines into account:
▪
Make sure to keep all stop valves open during operation.
▪
The gas and liquid stop valves are factory closed.
▪
The figures below show the name of each part required in handling the stop
valve.
a
b
c
d
a Service port and service port cover
b Stop valve
c Field piping connection
d Stop valve cover
a
b
e
d
c
a Service port
b Stop valve cover
c Hexagon hole
d Shaft
e Valve seat
▪
Do NOT apply excessive force to the stop valve. Doing so may break the valve
body.
Counterclockwise to open
Clockwise to close
Result: The valve is now open/closed.
▪
The stop valve cover is sealed where indicated by the arrow. Do NOT damage it.
▪
After handling the stop valve, tighten the stop valve cover securely, and check for
refrigerant leaks. For the tightening torque, refer to the table below.
18
Piping installation
|
Installer and user reference guide
75