18.2.7 Using the stop valve and service port

To handle the stop valve
To open/close the stop valve
To handle the stop valve cover
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482277-1B – 2020.10
Take the following guidelines into account:
Make sure to keep all stop valves open during operation.
The gas and liquid stop valves are factory closed.
The figures below show the name of each part required in handling the stop
valve.
a
b
c
d
a Service port and service port cover
b Stop valve
c Field piping connection
d Stop valve cover
a
b
e
d
c
a Service port
b Stop valve cover
c Hexagon hole
d Shaft
e Valve seat
Do NOT apply excessive force to the stop valve. Doing so may break the valve
body.
Counterclockwise to open
Clockwise to close
Result: The valve is now open/closed.
The stop valve cover is sealed where indicated by the arrow. Do NOT damage it.
After handling the stop valve, tighten the stop valve cover securely, and check for
refrigerant leaks. For the tightening torque, refer to the table below.
18
Piping installation
|
Installer and user reference guide
75