  • Page 1 Technical Data Book Wind-Free 1Way Cassette for Global (R410A, 50Hz) Model : AM∗∗∗NN1∗EH/∗∗...
  • Page 2 History Version Modification Date Remark Ver. 1.0 Release VRF Wind-Free 1Way Cassette for Global TDB (50Hz) '17. 11. 22 Ver. 1.1 Revised some errors of panel Weight/Shipping Dimensions. '18. 04. 19 Ver. 1.2 Added Wind-Free Performance Characteristics in Summary Table '18.
  • Page 3 Nomenclature Indoor Units Model Names ∗∗ Buyer (1) Classification (5) Product Notation 1Way Cassette (6) Feature (2) Capacity Premium X 100 Watt (3 digits) Deluxe (3) Version (7) Rating Voltage 2016 1Ø, 220~240V, 50Hz 2017 2018 (8) Mode Heat Pump (R410A) (4) Product Type Indoor Unit Outdoor Unit...
  • Page 4 Living room ※ Wind-Free implementation : Still air by the velocity of flow below 0.15m/s. ※ Expand the blade angle from 30˚ to 80˚ Conventional product (Samsung) : 40~80 ˚ 2. Big blade Max. 8m Horizontal reach Conventional 68 mm...
  • Page 5: Table Of Contents

    Contents 1. Line up 2. Specification 3. Summary Table 4. Capacity Table 5. Dimensional Drawing 6. Center of Gravity 7. Electrical Wiring Diagram 8. Sound data 9. Temperature and Air Flow Distribution 10. Piping Diagram 11. Installation 12. Accessory...
  • Page 6: Line Up

    1. Line up Wind free 1 Way Cassette Capacity (kW) Wind free 1 Way Cassette Type Small Middle Large Model Name AM017NN1PEH/∗∗ AM022NN1PEH/∗∗ AM022NN1DEH/∗∗ AM028NN1DEH/∗∗ AM036NN1DEH/∗∗ AM056NN1DEH/∗∗ AM071NN1DEH/∗∗...
  • Page 7: Specification

    2. Specification Wind free 1 Way Cassette Type 1Way CASSETTE 1Way CASSETTE Model Name AM017NN1PEH/∗∗ AM022NN1PEH/∗∗ Power Supply Φ, #, V, Hz 1,2,220-240,50 1,2,220-240,50 Mode HP/HR HP/HR 1.70 2.20 Cooling Btu/h 5,800 7,500 Performance Capacity 1.90 2.50 Heating Btu/h 6,500 8,500 Cooling 24.00...
  • Page 8 2. Specification Wind free 1 Way Cassette Type 1Way CASSETTE 1Way CASSETTE Model Name AM017NN1PEH/∗∗ AM022NN1PEH/∗∗ Casing Material Model Name PC1MWFMAN PC1MWFMAN Type Wind Free Wind Free Material HIPS HIPS Color White White Panel Net Weight Shipping Weight Net Dimensions (W×H×D) 960 x 35 x 420 960 x 35 x 420 Shipping Dimensions (W×H×D)
  • Page 9 2. Specification Wind free 1 Way Cassette Type 1Way CASSETTE 1Way CASSETTE 1Way CASSETTE Model Name AM022NN1DEH/∗∗ AM028NN1DEH/∗∗ AM036NN1DEH/∗∗ Power Supply Φ, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50 Mode HP/HR HP/HR HP/HR 2.20 2.80 3.60 Cooling Btu/h 7,500 9,600 12,300 Performance Capacity 2.50 3.20...
  • Page 10 2. Specification Wind free 1 Way Cassette Type 1Way CASSETTE 1Way CASSETTE 1Way CASSETTE Model Name AM022NN1DEH/∗∗ AM028NN1DEH/∗∗ AM036NN1DEH/∗∗ Casing Material Model Name PC1NWFMAN PC1NWFMAN PC1NWFMAN Type Wind Free Wind Free Wind Free Material HIPS HIPS HIPS Color White White White Panel Net Weight...
  • Page 11 2. Specification Wind free 1 Way Cassette Type 1Way CASSETTE 1Way CASSETTE Model Name AM056NN1DEH/∗∗ AM071NN1DEH/∗∗ Power Supply Φ, #, V, Hz 1,2,220-240,50 1,2,220-240,50 Mode HP/HR HP/HR 5.60 7.10 Cooling Btu/h 19,100 24,200 Performance Capacity 6.30 8.00 Heating Btu/h 21,500 27,300 Cooling 55.00...
  • Page 12 2. Specification Wind free 1 Way Cassette Type 1Way CASSETTE 1Way CASSETTE Model Name AM056NN1DEH/∗∗ AM071NN1DEH/∗∗ Casing Material Model Name PC1BWFMAN PC1BWFMAN Type Wind Free Wind Free Material HIPS HIPS Color White White Panel Net Weight Shipping Weight Net Dimensions (W×H×D) 1410 x 35 x 500 1410 x 35 x 500 Shipping Dimensions (W×H×D)
  • Page 13: Summary Table

    3. Summary Table Wind free 1 Way Cassette Performance Characteristics Nominal Capacity(kW) Net Weight Airflow Sound Pressure Sound Power Model Code Fan Speed (kg) (CMM) (dBA) (dBA) Cooling Sensible Heating High 1.70 1.20 1.90 4.80 1.61 1.14 1.83 4.30 AM017NN1PEH/∗∗ 1.49 1.05 1.70...
  • Page 14: Capacity Table

    4. Capacity Table Wind free 1 Way Cassette Cooling TC : Total Capacity, SHC : Sensible Heat Capacity Indoor temperature (°C, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Model temperature (°C, DB) 1.20 1.00 1.40 1.10 1.60 1.20 1.70 1.20 1.80...
  • Page 15 4. Capacity Table Wind-Free 1Way Cassette Indoor temperature (°C, WB) Outdoor 14.0 16.0 18.0 19.0 20.0 22.0 24.0 Model temperature (°C, DB) 2.50 2.20 2.90 2.40 3.40 2.40 3.60 2.60 3.70 2.60 4.00 2.60 4.30 2.50 2.50 2.20 2.90 2.40 3.40 2.40 3.60...
  • Page 16 4. Capacity Table Wind-Free 1Way Cassette Heating TC : Total Capacity (kW) Indoor temperature (°C, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 Model (°C, DB) 1.10 1.10 1.10 1.10 1.10 1.20 1.20 1.20 1.20 1.20 1.30 1.20 1.20 1.20 1.20 1.40 1.40...
  • Page 17 4. Capacity Table Wind-Free 1Way Cassette Indoor temperature (°C, DB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 Model (°C, DB) 2.40 2.40 2.30 2.30 2.30 2.60 2.50 2.40 2.40 2.30 2.70 2.60 2.50 2.50 2.40 2.80 2.70 2.70 2.60 2.60 2.90 2.90 2.90...
  • Page 18: Dimensional Drawing

    5. Dimensional Drawing 5. Dimensional Drawing Wind-Free 1Way Cassette • AM017/022NN1PEH/∗∗ (Unit: mm) Ceiling opening dimension Space of suspension bolts Name Description Name Description Gas pipe connection Ø9.52 (3/8") Air outlet louver Liquid pipe connection Ø6.35 (1/4") Air inlet grille Drain hose connection VP20 (OD26, ID20) Power supply/Communication wiring...
  • Page 19 5. Dimensional Drawing Wind-Free 1Way Cassette • AM022/028/036NN1DEH/∗∗ (Unit: mm) Ceiling opening dimension 1150 1036 Space of suspension bolts 1198 Name Description Name Description Gas pipe connection Ø12.7 (1/2") Air outlet louver Liquid pipe connection Ø6.35 (1/4") Air inlet grille Drain hose connection VP20 (OD26, ID20) Power supply/Communication wiring...
  • Page 20 5. Dimensional Drawing Wind-Free 1Way Cassette • AM056/071NN1DEH/∗∗ (Unit: mm) Ceiling opening dimension 1380 1260 Space of suspension bolts Ceiling 1410 Name Description Name Description 5.2 kW Ø12.70 (1/2") Drain hose connection V25 (OD32, ID25) Gas pipe Power supply/Communication wiring connection 7.1 kW Ø15.88 (5/8")
  • Page 21: Center Of Gravity

    6. Center of Gravity Wind-Free 1Way Cassette (Unit: mm) Model AM017NN1PEH/∗∗ AM022NN1PEH/∗∗ AM022NN1DEH/∗∗ AM028NN1DEH/∗∗ 1,198 AM036NN1DEH/∗∗ AM056NN1DEH/∗∗ 1,410 AM071NN1DEH/∗∗...
  • Page 22: Electrical Wiring Diagram

    7. Electrical Wiring Diagram Wind-Free 1Way Cassette • AM022/028/036NN1DEH/∗∗ F100 FUSE Electronic expansion valve EVA-IN(10K) Thermistor EVA IN(10K) M[HALL IC] Motor (IDU fan) S-Plasma ion EVA-OUT(10K) Thermistor EVA OUT(10K) Thermal Fuse Terminal Block thermal fuse ROOM(10K) Thermistor ROOM(10K) NOTE • This wiring diagram applies only to the indoor unit. •...
  • Page 23 7. Electrical Wiring Diagram Wind-Free 1Way Cassette • AM017/022NN1PEH/∗∗, AM056/071NN1DEH/∗∗ F100 FUSE Electronic expansion valve EVA-IN(10K) Thermistor EVA IN(10K) M[HALL IC] Motor (IDU fan) S-Plasma ion EVA-OUT(10K) Thermistor EVA OUT(10K) Thermal Fuse Terminal Block thermal fuse ROOM(10K) Thermistor ROOM(10K) NOTE •...
  • Page 24: Sound Data

    8. Sound data 8. Sound data Wind-Free 1Way Cassette Sound Pressure level Unit: dB(A) Model High AM017NN1PEH/∗∗ AM022NN1PEH/∗∗ AM022NN1DEH/∗∗ Microphone AM028NN1DEH/∗∗ • NR Curve 1) AM017NN1PEH/∗∗ 2) AM022NN1PEH/∗∗ NR 50 NR 50 NR 45 NR 45 NR 40 NR 40 High High NR 35...
  • Page 25 8. Sound data Wind-Free 1Way Cassette Sound Pressure level Unit: dB(A) Model High AM036NN1DEH/∗∗ AM056NN1DEH/∗∗ AM071NN1DEH/∗∗ Microphone • NR Curve 1) AM036NN1DEH/∗∗ 2) AM056NN1DEH/∗∗ NR 50 NR 50 NR 45 NR 45 NR 40 NR 40 High High NR 35 NR 35 NR 30 NR 30...
  • Page 26 8. Sound data Wind-Free 1Way Cassette Sound Power level Unit: dB(A) NOTE Model High • Specifications may be subject to change without prior notice AM017NN1PEH/∗∗ - Sound power level is an absolute value that a sound source generates. AM022NN1PEH/∗∗ - dBA = A-weighted sound power level. AM022NN1DEH/∗∗...
  • Page 27 8. Sound data Wind-Free 1Way Cassette Sound Power level Unit: dB(A) NOTE Model High • Specifications may be subject to change without prior notice AM036NN1DEH/∗∗ - Sound power level is an absolute value that a sound source generates. AM056NN1DEH/∗∗ - dBA = A-weighted sound power level. AM071NN1DEH/∗∗...
  • Page 28: Temperature And Air Flow Distribution

    9. Temperature and Air Flow Distribution Wind-Free 1Way Cassette • AM017NN1PEH/∗∗ Cooling Air Velocity distribution Discharge angle : 60˚ Cooling temperature distribution Discharge angle : 60˚ Heating Air Velocity distribution Discharge angle : 60˚ Heating temperature distribution Discharge angle : 60˚...
  • Page 29 9. Temperature and Air Flow Distribution Wind-Free 1Way Cassette • AM022NN1PEH/∗∗ Cooling Air Velocity distribution Discharge angle : 60˚ Cooling temperature distribution Discharge angle : 60˚ Heating Air Velocity distribution Discharge angle : 60˚ Heating temperature distribution Discharge angle : 60˚...
  • Page 30 9. Temperature and Air Flow Distribution Wind-Free 1Way Cassette • AM022NN1DEH/∗∗ Cooling Air Velocity distribution Discharge angle : 60˚ Cooling temperature distribution Discharge angle : 60˚ Heating Air Velocity distribution Discharge angle : 60˚ Heating temperature distribution Discharge angle : 60˚...
  • Page 31 9. Temperature and Air Flow Distribution Wind-Free 1Way Cassette • AM028NN1DEH/∗∗ Cooling Air Velocity distribution Discharge angle : 60˚ Cooling temperature distribution Discharge angle : 60˚ Heating Air Velocity distribution Discharge angle : 60˚ Heating temperature distribution Discharge angle : 60˚...
  • Page 32 9. Temperature and Air Flow Distribution Wind-Free 1Way Cassette • AM036NN1DEH/∗∗ Cooling Air Velocity distribution Discharge angle : 60˚ Cooling temperature distribution Discharge angle : 60˚ Heating Air Velocity distribution Discharge angle : 60˚ Heating temperature distribution Discharge angle : 60˚...
  • Page 33 9. Temperature and Air Flow Distribution Wind-Free 1Way Cassette • AM056NN1DEH/∗∗ Cooling Air Velocity distribution Discharge angle : 60˚ Cooling temperature distribution Discharge angle : 60˚ Heating Air Velocity distribution Discharge angle : 60˚ Heating temperature distribution Discharge angle : 60˚...
  • Page 34 9. Temperature and Air Flow Distribution Wind-Free 1Way Cassette • AM071NN1DEH/∗∗ Cooling Air Velocity distribution Discharge angle : 60˚ Cooling temperature distribution Discharge angle : 60˚ Heating Air Velocity distribution Discharge angle : 60˚ Heating temperature distribution Discharge angle : 60˚...
  • Page 35: Piping Diagram

    10. Piping Diagram Wind-Free 1Way Cassette Indoor Fan Motor (IFM) Electronic Expansion valve - Indoor unit Thermistor - (E_IDU) Relative Humidity (T_RH) Filter Thermistor - Liquid pipe connection port Heat Exchanger - Heat Exchanger Ø A Indoor unit Thermistor - (HX_ID) (T_II) Thermistor -...
  • Page 36: Installation

    11. Installation Wind-Free 1Way Cassette Step 1 Installing the indoor unit CAUTION When deciding on the location of the air conditioner the • Make sure that the ceiling is strong enough to following restrictions must be taken into account. support the weight of the indoor unit. Before hanging the unit, test the strength of each attached 1 Place the pattern sheet on the ceiling at the spot suspension bolt.
  • Page 37 11. Installation Wind-Free 1Way Cassette 7 Adjust the unit to the appropriate position, taking Made vacuum for 15 minutes and pressurizing system into account the installation area for the front panel. with nitrogen. • Place the pattern sheet on the indoor unit. •...
  • Page 38 11. Installation Wind-Free 1Way Cassette CAUTION • Must fit tightly against body without any gap. • Install the insulation not to get wider and use the adhesives on the connection part of it to prevent moisture from entering. • Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. •...
  • Page 39 11. Installation Wind-Free 1Way Cassette • When installing insulation in the places and PVC Tube Joint conditions below, use the same insulation that is Drain hose + VP25 (OD: 32 mm, ID: 25 mm) used for high humidity conditions. <Geological condition> VP 20 (Drain pipe) High humidity locations such as shorelines, hot (OD: 26mm, ID: 20mm)
  • Page 40 11. Installation Wind-Free 1Way Cassette • Do not give the hose an upward gradient beyond • Max. allowable aixs gap the connection port. This will cause water to flow backwards when the unit is stopped, resulting in water leaks. Under gradient Indoor unit Max.
  • Page 41 11. Installation Wind-Free 1Way Cassette Step 4 Connecting the power and communication cables Power and communication cable connection • Before wiring work, you must turn off all power source. • Connect the power and communication cable among the units within maximum length to set the voltage drop under 10%.
  • Page 42 11. Installation Wind-Free 1Way Cassette Selecting the crimping terminal lug 1 Select the crimping terminal lug based on the norminal dimension of the power cable. 2 Cover the connection part of the power cable and crimping terminal lug to insulate it. Silver solder Norminal Norminal...
  • Page 43 11. Installation Wind-Free 1Way Cassette Specifications of the terminal blocks Rated currents Model Rating current(A) (Unit: mm) AM017NN1PEH∗ 0.14 Communication: M3.5 screw AC power: M4 screw AM022NN1PEH∗ 0.15 AM022NN1DEH∗ 0.20 AM028NN1DEH∗ 0.23 AM036NN1DEH∗ 0.25 AM056NN1DEH∗ 0.28 Power supply MCCB AM071NN1DEH∗ 0.40 (single phase) Min : 198V...
  • Page 44: Accessory

    12. Accessory Wind-Free 1Way Cassette Controller Classification Product Model Image Remark Using Wireless Remote AR-EH03E DVM, CAC Controller Wired Remote MWR-WE11N DVM, CAC Controller Wired Remote MWR-SH00N DVM, CAC Controller - Simple Type Wired Remote MWR-SH10N DVM, CAC Controller - Touch Simple Type ERV Wired MWR-VH12N...
  • Page 45 12. Accessory Wind-Free 1Way Cassette Classification Product Model Image Remark Using Onoff Controller MCM-A202DN DVM, CAC Touch Centralized MCM-A300N DVM, CAC Controller WIFI KIT MIM-H03N DVM, CAC Centralized Control System Interface Module MIM-N01 DVM, CAC ERV Interface MIM-N10 DVM, CAC Module DMS2.5 MIM-D01AN...
  • Page 46 S-Converter MIM-C02N DVM, CAC run Solution External Room MRW-TA DVM, CAC Sensor Others Operation Mode MCM-C200 Selection Switch NOTE • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.Samsung.com site.
  • Page 47 MXD-E32K200A MXD-E24K232A MXD-E24K300A 3 Indoor MXD-E32K224A MXD-E32K300A MXD-A38K2A 8~12 HP PDM KIT MXD-A12K2A 14~16 HP MXD-A58K2A 18~26 HP NOTE • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.Samsung.com site.
  • Page 48 [Option] Duct S, Big Duct, ERV, ERV Plus Motion detect Sensor MCR-SMA 4Way Cassette S (600x600) External room sensor MRW-TA Casssette, Wall-mount, Ceiling, Duct, Console NOTE • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.Samsung.com site.
  • Page 49 Ver.1.2.1 Samsung Electronics Co., LTD. B2B PM / SE Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677 Website : www.samsung.com, http://btsp.samsunggsbn.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.