Unit configuration

6.7 Configuration by program

Sample program (AFP7AD4H)
36
With the analog unit it is possible to make configuration settings by user
program. Please refer to the appendix for the bit settings of each parame-
ter (see p. 42).
To change the configuration, make the desired bit settings in the unit
memory of the corresponding parameter and write "16#55AA" to unit
memory UM00028.
After the configuration has been updated, unit memory UM00028 will be
set to 0.
Make the following settings by user program:
Analog output processing, channel 0–1: Enable
Analog output processing, channel 2–3: Disable
Range setting: 4–20mA