Status Flags - Panasonic FP7 User Manual

Analog output unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

1)
Digital input value
2)
Clipping control flag

8.3.2 Status flags

1)
Error flag
2)
Upper limit clipping flag
FP7 Analog Output Unit User's Manual
Memory area for digital values before conversion into the analog output
values. If scale conversion has been set, the corresponding scaled values
are stored here.
Voltage range
-10 to +10V
0 to +10V or 0 to 5V
+1 to +5V
TRUE to execute the upper and lower limit clipping function.
FALSE to turn the upper limit clipping flag (Xn1) and the lower limit clipping
flag (Xn2) to FALSE.
Status flags are allocated to the CPU's input area (WX).
The I/O addresses in the table show offset addresses. I/O addresses actu-
ally allocated are based on the first word number allocated to the unit.
Example: If the first word number is 10, the address number for the error
flag on channel 0 will be X100.
Address
Channel 0
Channel 1
WX0 X0
WX1 X10
X1
X11
X2
X12
X3–XF
X13–X1F
TRUE when an error has occurred.
TRUE when the digital input value exceeds the upper limit clipping value,
provided that the clipping function is active.
Current range
0 to +20mA
+4 to +20mA
Channel 2
Channel 3
WX2 X20
WX3 X30
X21
X31
X22
X32
X23–X3F
X33–X3F Not used
Specifications
Digital input value
-31250 to +31250
0 to +31250
0 to +25000
0 to +31250
0 to +25000
Name
1)
Error flag
Upper limit clipping
2)
flag
Lower limit clipping
3)
flag
41