Correct operation of the solar cell can be checked by covering the solar cell for at
least one minute and checking that the controller (suitably configured to allow
dimming) dims the signals. Remove the cover and check that the signals return to
the bright condition.
7.5.14 Junction System Testing
Using the detect lights on the above ground detectors, ensure that all above ground
detectors (Kerbside and On-Crossing) are functional and have the required zone of
detection.
Using the web page:
Status and Configuration → Controller → I/O → Lines
Or the Handset command "IOP", check that all road detector loops, Above Ground
Detector demand pushbuttons etc are correctly connected.
Clear all faults in the log and allow the junction to run normally. Periodically check
the fault table / system log and ensure that no faults are raised. Verify that the
controller has the correct date and time and is keeping correct time.
7.5.15 Site Information Export (PI dump)
Various configuration and status information can be exported from the controller to
be reviewed and stored using the 'Export Site Information' button on the System
web page. This can be used to collect information as part of a periodic inspection
(sometimes referred to as a 'PI dump').
Press the 'Export Site Information' button to download a zip file containing all of the
site information. The filename generated is based on the following:
'Unique Site Name' that can be set on the web page:
Status and Configuration → System → Settings → Comms → DSL/Fibre
followed by '_dateTtime_siteinfo.zip' where date and time are the exported date and
time.
Once downloaded the zip file can be unzipped into a folder. The user can navigate
the downloaded file set by opening index.html in a web browser.
7.5.16 Loading New Firmware
If new firmware is required refer to the ST950 User Interface Handbook
667/HU/46000/000 for how to load new firmware.
7.6

Customer Acceptance

Run through the commissioning with the customer. The Controller Data page of the
site information export contains important controller settings which the customer
should review and accept as part of the acceptance procedure.
Security classification
Version
Last Editor
Document Name
Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
Use with Care!
Dim signals may be difficult for road users to see during daylight hours
Unrestricted
5
Neil Atkinson
ST950 ICM Handbook
Intelligent Traffic Systems
Sopers Lane, Poole, Dorset, BH17 7ER
Page
82 of 125
Status
Issued
Date
18-Dec-2018
Document No.
667/HE/46950/000

Advertisement

Table of Contents
loading

Table of Contents