All 16 relays are rated for dry contact signal or load switching. While they are sized
to handle typical loads, load switching can cause abnormal contact wear and pre-
mature contact failure. Switching of inductive loads (e.g., strikes) also causes EMI
(electromagnetic interference) which may interfere with normal operation of other
equipment. To minimize premature contact failure and to increase system reliabil-
ity, a contact protection circuit is recommended. The following two circuits are sug-
gested. Locate the protection circuit as close to the load as possible (within 12
inches [30cm]); the effectiveness of the circuit decreases as the distance from the
load increases.
Relays 12 through 15 are general purpose relay outputs and are not available
when the board is rack-mounted.
Use sufficiently large gauge of wires for the load current to avoid voltage loss.

Mounting Options

This board can be mounted on-edge in the rack-mount enclosure provided by
Honeywell, or it can be mounted flat against any surface using standoffs under the
mounting holes provided in each of the four corners of this board.
When this board is rack-mounted, the connectors for four general-purpose out-
puts and two dedicated inputs are not accessible and should not be used.
The most likely reason for mounting a board flat is that it is being installed
remotely to be located near the door(s) being monitored. In this case, mount it in its
own enclosure. Use the two dedicated inputs to monitor cabinet tamper and power
fault.
The four additional general-purpose outputs allow for control of local horns or
other equipment.

Installing the Module

Step 1.
Step 2.
Step 3.
Step 4.
Warning: DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET
PW-7000 Output Module (PW7K1OUT) Installation Guide, Document 800-25675V1
Set Jumpers and DIP switches.
Mount this board in the appropriate enclosure. If this board is being
mounted in a rack, the component side of the board is to your right as you
face the rack.
Connect the communications and power supply to the circuit boards with
the Power Supply Harness.
Connect wiring to input sensors or install jumper wire as appropriate.
UNTIL ALL WIRING HAS BEEN INSTALLED AND RECHECKED.