Before installing the heat pump, check that the pool supply impedance does not exceed 0.042 Ω.
Consult your electricity supplier if necessary.
If the energy supplier is unable to change the impedance level, this may translate to a voltage drop of several
seconds when starting the pump.
Maximum water pressure: 2 bar (29 PSI).

Assembly

Assembly conditions

Place of installation
The pool heat pump should be installed outside the buildings, more than 2 m from the pool, in
accordance with applicable law (NF C 15 100).
Install the pump on a flat, level and stable surface. (Concrete substrate is ideal).
There must be a completely free space of at least 1 m (40 in) / a minimum of 30 cm (12 in) at the rear of the unit
(evaporator air inlet) and a minimum of 3 m (120 in) on the exhaust side of the fan.
It must be ensured that the removed air is not drawn back into the evaporator. Sufficient
space must be maintained for access to the temperature controller.
So that the assembly is optimal
Avoid directing the ventilation air stream to noise-sensitive zones (e.g. room windows) or to places where people are
usually present (air blown out is cold).
Avoid placing the pump on surfaces that transmit vibrations.
Avoid placing the device under trees or in places exposed to water or mud - this may cause problems during the
operation and maintenance of the device.
For optimal operation of the unit, the water pipes from the heat pump to the pool should be insulated, especially if the
pump is located at a great distance from the pool.
Inlet air flow:
1 m / min. 30 cm
Air flow at the outlet: Free space /
min. 3 m (120 inches)
- 5 -