Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from the date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
The 82-5221 is a fixed-mounted device with a relay, stack light, and emergency stop button. It requires 115 VAC to operate. A relay inside the 82-5221 is field-wired into the power line of a user-supplied solenoid valve. When the emergency stop button on the front of the housing door is pushed, power to the connected solenoid valve is cut off.
Figure 1: External Component Location Housing The 82-5221’s PBT/PC blend housing is weather- and corrosion-resistant. It is suitable for installation where general purpose equipment is in use. The housing door is hinged on the left side and is secured by two latches on the right side. A panel inside the housing allows for component installation and mounting.
Terminal Strip Figure 2: Internal Component Location Relay A DPDT relay installed on the right side of the 82-5221 controls the stack light’s LED color and also controls the power to the solenoid valve. Power Supply An AC/DC power supply installed on the left side of the 82-5221 converts user-supplied 115 VAC to the 24 VDC that the 82-5221 requires for operation.
Field Wiring Terminal Strip The relay and emergency stop button connections are wired to a terminal strip located in the lower right corner of the 82-5221. The terminal strip makes wiring to the solenoid valve and a remote relay contact (optional) more accessible.
Page 8
4. Insert 3/16 in. screws through the mounting slots to secure the housing to the mounting surface. 7.19 Ø .23 x .3 slot, 4X 18.77 11.41 6.04 3/4 NPT Conduit Hub 8.09 Figure 3: Outline & Mounting Dimensions 8 • 82-5221...
Green Yellow Relay Black Emergency Stop Power Supply Button C ontacts 1 N C SO L ENO ID T O AL AR M C ON T RO L C ON T ACT S Figure 4: Factory Wiring 82-5221 • 9...
Connecting the 82-5221 to a remote relay contact is is not necessary for operation. Connecting the 82-5221 to a remote relay contact provides another way to cut the power line to the solenoid valve. If you do connect the 82-5221 to a remote relay contact, the relay contact set used must be normally open and the relay must be configured as normally energized.
Page 11
(as shown in Figure 5 and Figure 6 below). When the relay contact is closed, power is supplied to the solenoid valve. When the relay contact opens, the power line to the solenoid valve is cut. NOTE: The relay that you connect to the 82-5221 must be configured as normally energized. Power Supply...
Page 12
Solenoid Valve NOTE: If rem ote relay contacts are not wired to the F ield W iring Terminal Strip, leave the jumper installed. Relay Contacts Figure 6: Field Wiring, AC-Powered Solenoid Valve 16. Close the housing door. 12 • 82-5221...
1. Be sure the emergency stop button is not pushed. If it is pushed, turn it clockwise to reset it. 2. Turn on power to the 82-5221, power to the solenoid valve, and power to the device whose relay contact is wired to the 82-5221 (if used).
9. Use a new zip tie to connect the fuse holder to the right side of the housing. 10. Close the housing door. 11. Plug in or connect power to the 82-5221. Parts List Table 2 lists replacement parts and accessories for the 82-5221. Table 2: Parts List Part Number Description...