Installation; Preparing The Space; Placing The Cabinet; Installing The Unit - Perlick HP15 Installation Instructions Manual

Hide thumbs Also See for HP15:
Table of Contents

Advertisement

PERLICK RESIDENTIAL UNDERCOUNTER INSTALLATION MANUAL

PREPARING THE SPACE

If the unit is to be installed under
CAUTION
a countertop, it is recommended
that the countertop be supported by surrounding
cabinetry and use shims to support countertop
directly above the refrigerated cabinet.
Make sure the floor under the
CAUTION
unit is level with the surrounding
finished floor. Protect a finished floor with plywood,
cardboard, or some other suitable material before
moving the unit into place. Failure to do this may result
in damage to the floor.

PLACING THE CABINET

To assure maximum performance, fresh air must
be allowed to circulate through the machinery
compartment. Do not place anything in front of the
cabinet that would obstruct air flow at these grilles. Do
not place the unit in an unventilated small room.
Cabinet should be leveled front to
NOTICE
back then side to side
1). Make sure the space opening is correctly sized for
the unit. See chart below for finished rough opening
requirements:
HP15 15" Signature Series
Height
34-3/8" minimum,
35-1/2" maximum
HP24 24" Signature Series
Height
34-3/8" minimum,
35-1/2" maximum
HH24 Signature Shallow Depth
Height
32-1/2"
HC24 24" C-Series
Height
34-3/8" minimum,
35-1/2" maximum
HA24 24" ADA-Compliant Series
Height
32-1/2"
NOTE: For a cabinet door to open properly, the door must open a
minimum of 90°. Use a minimum 3" filler in corner installations to
assure a full 90° opening. Allow 25" clearance in front of unit for full
door swing and shelf/drawer pull out for all units.
6 | perlick.com/residential
Depth
Width
24"
15"
Depth
Width
24"
24"
Depth
Width
18"
24"
Depth
Width
24"
24"
Depth
Width
24"
24"
2). Check that the following are level and square:
• Front and interior opening
• Installation opening and floor surface
• Countertop bottom front edge
NOTE: The floor under the unit must be at the same level as the
surrounding finished floor.
To prevent possible damage to
CAUTION
the countertop, do not place
heavy objects on countertop directly over unit.

INSTALLING THE UNIT

1) Plug the unit into the 15 amp grounded electrical
outlet located within the installation opening. With
power applied to the unit, check that the lighting and
cooling functions operate properly. Turn off the power
to the wall outlet at the circuit breaker.
2) With all surfaces in the installation opening square
and level, refer to Figure 4 on page 7 and perform the
following steps to level the unit:
• At the front of the opening, measure from the floor to
the bottom of the front edge of the countertop.
• Measure from the floor surface to the top of the unit
at the rear corners.
• Adjust the unit legs so these two measurements are
equal. Using an adjustable wrench or pliers, turn legs
clockwise to lower the unit or counterclockwise to raise it.
NOTE: Legs should not extend more than 3/4" from the bottom
of the unit.
3) Slide the unit into position in the opening. Make sure
the rear leveling legs slide under the ant-tip brackets.
Push the unit into the opening until the bottom front
edge of the unit is flush with the surrounding cabinetry,
or until the rear legs are tight against the anti-tip
brackets.
4) Shim the front of the unit so the front face is flush
with the surrounding cabinetry. Adjust the front legs to
support the countertop at the shimmed height. Using
an adjustable wrench or pliers, turn the legs clockwise to
lower the unit or counterclockwise to raise it. Countertop
should be resting on top of the unit.
NOTE: Countertop should be resting evenly on entire top of the
unit. Shim if necessary to prevent damage to the countertop.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents