Error code:
Description:
Cause and Remedy:
Display:
Error code:
Description:
Cause and Remedy:
Display:
Error code:
Description:
Cause and Remedy:
Description:
Cause and Remedy:
Display:
Error code:
Description:
Cause and Remedy:
200013_EN 2.0
Flame return gate does
not reach CLOSE limit
switch
no signal although
closed
12
Both flame return gate limit switches are closed at the same time
both limit switches
activated
14
Container cover open
Cover open
End-switch defect
15
DHW sensor fracture, measuring circuit from DHW sensor is open
sensor not connected
sensor defect
sensor cable defect
sensor temperature too
high
DHW sensor short circuit, measuring circuit from boiler sensor is shorted out
sensor defect
sensor cable defect
sensor temperature too
low
16
Sensor break accumulator sensor, measuring circuit of acculmulator sensor is
open
sensor not connected
sensor defect
check whether ball valve is jammed, check ball
valve throughway to see if foreign objects are
preventing it from closing
check cables and flame return gate
check flame return gate, check cables, check
connectors
close cover
replace end-switch
connect sensor at input
measure sensor (approx. 2k at 25° C) replace if
required
replace sensor
sensor temperature above measuring range
(1100° C)
measure sensor (approx. 2k at 25° C) replace if
required
replace sensor
sensor temperature below measuring range (-
10° C)
connect sensor at input
measure sensor (approx. 2k at 25° C) replace if
required