11 Diagnostics and servicing
Code
Cause
Text message
F080
General software error
General software
error
F105
The instrument is still in the start
phase, the measured value could
Determine meas-
not yet be determined
ured value
F113
EMC interference
Communication
error
F125
Temperature of the electronics in
the non-specified range
Impermissible elec-
tronics temperature
F260
Error in the calibration carried out
in the factory
Error in the cali-
bration
Error in the EEPROM
F261
Error during setup
Error in the instru-
False signal suppression faulty
ment settings
Error when carrying out a reset
F264
Adjustment not within the vessel
height/measuring range
Installation/Setup
error
Max. measuring range of the in-
strument not sufficient
F265
Sensor no longer carries out a
measurement
Measurement func-
tion disturbed
Operating voltage too low
Function check
Code
Cause
Text message
C700
A simulation is active
Simulation active
Out of specification
Code
Cause
Text message
S600
Temperature of the electronics in
the non-specified range
Impermissible elec-
tronics temperature
36
Rectification
Disconnect operating voltage
briefly
Wait for the end of the switch-on
phase
Duration up to approx. 3 minutes
depending on the version and pa-
rameter settings
Remove EMC influences
Check ambient temperature
Insulate electronics
Use instrument with higher tem-
perature range
Exchanging the electronics
Send instrument for repair
Repeat setup
Carry out a reset
Check or correct installation and/
or parameter settings
Use an instrument with bigger
measuring range
Check operating voltage
Carry out a reset
Disconnect operating voltage
briefly
Rectification
Finish simulation
Wait for the automatic end after
60 mins.
Rectification
Check ambient temperature
Insulate electronics
VEGAPULS 21 • Two-wire 4 ... 20 mA/HART
DevSpec
State in CMD 48
Bit 5 of Byte 0 ... 5
Bit 6 of Byte 0 ... 5
Bit 12 of Byte 0 ... 5
Bit 7 of Byte 0 ... 5
Bit 8 of Byte 0 ... 5
Bit 9 of Byte 0 ... 5
Bit 10 of Byte 0 ... 5
Bit 11 of Byte 0 ... 5
DevSpec
State in CMD 48
"Simulation Active"
in "Standardized
Status 0"
DevSpec
State in CMD 48
Byte 23, Bit 4 of
Byte 14 ... 24