3 | Areas of application

3.1 Refrigerants

• HFKW / HFC:
• HFCKW / HCFC:

3.2 Oil charge

The compressors are factory-filled with the following oil type:
- for R134a, R404A/R507, R407C, R513A
- for R22
Compressors with ester oil charge (BOCK lub E55) are marked with an X in the type designation (e.g.
FKX30/325 N).

3.3 Limits of application

D
GB
F
I
Tr
Ru
8
R134a, R404A/R507, R407C, R514A,
R22
INFO
For recharging, we recommend the above oil types. See lubricants
table, Chapter 6.6.
ATTENTION Compressor operation is possible within the operating limits.
These can be found in Bock compressor selection tool (VAP)
under vap.bock.de. Observe the information given there.
- Max. permissible discharge end temperature: 140°C
- Permissible ambient temperature: (-20°C) - (+100°C)
- Max. permissible switching frequency: 12 x /h
- A minimum running time of 2 min. at equilibrium (continuous
operation) must be achieved.
Avoid continuous operation near the threshold. Should the com-
pressor happen to be used near the thresholds, we recommend the
use of a thermal protection thermostat (Accessories, Chap. 7).
When operating in the vacuum range, there is a danger of air en-
tering on the suction side. This can cause chemical reactions, a
pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!
R452A
BOCK lub E55
BOCK lub A46