Checking the gas connections for tightness
5. Check for tightness:
Outlet joints of the gas train
Joint between the fan and the fitting
Joint between the fan and the supply air collector
Service instructions for the "MatriX-Disk
burner"
!
Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into contact
with electrical contacts.

Cleaning the condensate drain pipe and trap

Note
Clean the condensate drain pipe and trap at least once
a year.
1. Disconnect neutralising system condensate drain
hose
B
from trap
A
.
2. Connect the cleaning hose to the trap and route it
to the drainage system.
3. Clean the inside of the condensate drain pipe
(hose, pipes) and trap
.
A
Commissioning, inspection, maintenance
(cont.)
Note
Only use suitable and approved leak detection agents
(EN 14291) and devices for the tightness test. Leak
detection agents with unsuitable constituents (e.g.
nitrides, sulphides) can cause material damage.
Remove residues of the leak detection agent after test-
ing.
A
B
Fig. 6
4. Fill the lower section of trap
secure.
Danger
If the trap is not full, flue gas can escape.
Escaping flue gas can cause life threatening
carbon monoxide poisoning.
Always fill the trap with water.
5. Reconnect the condensate drain hose for the neu-
tralising system to the trap. Route the condensate
drain hose without kinks and with a constant fall.
A
with water and
19