Commissioning, inspection, maintenance
Cleaning the condensate drain pipe and trap and reconnecting to the
drainage system
1. Before installation, check the stench trap and con-
densate drain for contamination and clean if
required.
Danger
Escaping flue gas poses a risk to health.
Always connect the condensate drain with a
stench trap to prevent flue gas escaping.
2. Check that the hoses are routed without kinks and
that the condensate can drain freely.
Note
Always route the condensate pipe with a constant
fall.

Filling the trap with water

Fig. 11
Remove the supply hose (to the trap) from the boiler
condensate drain and fill with a little water.
Checking connections and sensor well on the heating water side for tight-
ness

Checking the function of the safety equipment

16
3. Check the neutralising system (accessories).
Neutralising system installation and operat-
ing instructions