CAPACITIES AND SELECTION DATA
3-38
POSSIBLE
COMBINATIONS
TOTAL
CAPACITY RATING
TO OPERATE
(kW)
1.5+1.5+1.5
4.5
1.5+1.5+1.8
4.8
1.5+1.5+2.5
5.5
1.5+1.5+3.5
6.5
1.5+1.5+5.0
8.0
1.5+1.8+1.8
5.1
1.5+1.8+2.5
5.8
1.5+1.8+3.5
6.8
1.5+1.8+5.0
8.3
1.5+2.5+2.5
6.5
1.5+2.5+3.5
7.5
1.5+3.5+3.5
8.5
1.8+1.8+1.8
5.4
1.8+1.8+2.5
6.1
1.8+1.8+3.5
7.1
1.8+2.5+2.5
6.8
1.8+2.5+3.5
7.8
2.5+2.5+2.5
7.5
2.5+2.5+3.5
8.5
COOLING
TOTAL INPUT
(kW) (RANGE)
TOTAL
1.50+1.50+1.50
4.50
1350
(2.20-5.00)
(800-1750)
1.50+1.50+1.80
4.80
1450
(2.20-5.50)
(800-1800)
1.45+1.45+2.41
5.30
1680
(2.20-6.00)
(800-2100)
1.22+1.22+2.85
5.30
1970
(2.20-6.00)
(800-2160)
0.99+0.99+3.31
5.30
2100
(2.20-6.00)
(800-2160)
1.50+1.80+1.80
5.10
1970
(2.20-5.60)
(800-1950)
1.37+1.64+2.28
5.30
2100
(2.20-6.00)
(800-2160)
1.17+1.40+2.73
5.30
2100
(2.20-6.00)
(800-2160)
0.96+1.15+3.19
5.30
1690
(2.20-6.00)
(800-2160)
1.22+2.04+2.04
5.30
1870
(1.50-6.00)
(800-2160)
1.06+1.77+2.47
5.30
2100
(2.20-6.00)
(800-2160)
0.94+2.18+2.18
5.30
1970
(2.20-6.00)
(800-2160)
1.77+1.77+1.77
5.30
1690
(2.20-5.90)
(800-2050)
1.56+1.56+2.17
5.30
1870
(2.20-6.00)
(800-2160)
1.34+1.34+2.61
5.30
2100
(2.20-6.00)
(800-2160)
1.40+1.95+1.95
5.30
1970
(2.20-6.00)
(800-2160)
1.22+1.70+2.38
5.30
2100
(2.20-6.00)
(800-2160)
1.77+1.77+1.77
5.30
2100
(2.20-6.00)
(800-2160)
1.56+1.56+2.18
5.30
2100
(2.20-6.00)
(800-2160)
OUTDOOR UNIT
CAPACITY
AMPERE(A)
EER
RATING
(kW) (RANGE)
(W)
220V 230V 240V
6.2
5.9
5.7 3.33 2.00+2.00+2.00
(2.40-6.50)
6.7
6.4
6.1 3.31 1.94+1.94+2.42
(2.20-6.60)
7.7
7.4
7.1 3.15 1.70+1.70+2.89
(2.20-6.60)
9.0
8.7
8.3 2.69 1.52+1.52+3.26
(2.20-6.60)
9.6
9.2
8.8 2.52 1.20+1.20+3.90
(2.40-6.60)
9.0
8.7
8.3 2.59 1.80+2.25+2.25
(2.40-6.60)
9.6
9.2
8.8 2.52 1.59+1.99+2.71
(2.40-6.60)
9.6
9.2
8.8 2.52 1.43+1.79+3.08
(2.40-6.60)
7.8
7.4
7.1 3.14 1.15+1.43+3.72
(2.40-6.60)
8.6
8.2
7.9 2.83 1.43+2.43+2.43
(2.40-6.60)
9.6
9.2
8.8 2.52 1.30+2.21+2.79
(2.40-6.60)
9.0
8.7
8.3 2.69 1.19+2.56+2.56
(2.40-6.60)
7.8
7.4
7.1 3.14 2.10+2.10+2.10
(2.40-6.60)
8.6
8.2
7.9 2.83 1.88+1.88+2.55
(2.40-6.60)
9.6
9.2
8.8 2.52 1.69+1.69+2.91
(2.40-6.60)
9.0
8.7
8.3 2.69 1.69+2.30+2.30
(2.40-6.60)
9.6
9.2
8.8 2.52 1.54+2.10+2.66
(2.40-6.60)
9.6
9.2
8.8 2.52 2.10+2.10+2.10
(2.40-6.60)
9.6
9.2
8.8 2.52 1.93+1.93+2.44
(2.40-6.60)
HEATING
OUTDOOR UNIT
AMPERE(A)
TOTAL INPUT
at 220V-240V
(W)
TOTAL
220V 230V 240V
[1]
6.00
1900
8.7
8.3
(1500-2250)
6.30
1950
9.0
8.6
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
6.30
1980
9.1
8.7
(1500-2250)
COP
8.0
3.16
8.2
3.23
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18
8.3
3.18