Stack Voltage Faults - Nuvation Energy NUVSSG-1250-100 Product Manual

High-voltage bms
Table of Contents

Advertisement

The Stack Switchgear is configured for a specific battery topology based on the
details provided to Nuvation Energy during order fulfillment. Failure to use the same
number of Cell Interface modules and/or using a different battery topology could
result in initialization issue and other undesirable behavior. Please contact
support@nuvationenergy.com
require a Stack Switchgear configuration update.
1. Missing or misconfigured Cell Interface modules, preventing the software from scanning for the
measurements
2. Misconfiguration on the number of Cell Interface modules. Refer to the register sc_linkbus.cicount
(Note that Low-Voltage BMS is counted as a Cell Interface).
3. Failure in the Link Bus communication. Any interruptions of the bus can prevent the cell voltages
from being initialized. Such a failure could happen if:
Not all Cell Interface modules are connected
Link Bus cables are connected to the wrong port (i.e. Link Out instead of Link In).
Link Bus cables are damaged

10.1.2. Stack Voltage Faults

stack_fault_voltage_over
Fault that is triggered when the stack voltage is above the over fault threshold.
stack_fault_voltage_hi
Fault that is triggered when the stack voltage is above the high fault threshold.
stack_fault_voltage_lo
Fault that is triggered when the stack voltage is below the low fault threshold.
stack_fault_voltage_under
Fault that is triggered when the stack voltage is below the under fault threshold.
stack_fault_voltage_sum
Fault that is triggered when the absolute difference between the measured stack voltage and
sum of all cell voltages in the stack exceeds the fault threshold.
10.1.2.1. Initialization Issues
These faults have the following initialization issues:
Fault
stack_fault_voltage_hi
stack_fault_voltage_lo
stack_fault_voltage_sum
Document ID: NE-PM-003
if there is a change in the system design that would
Initialization Issues
Contact support@nuvationenergy.com. Stack Switchgear unit's internal Power Interface module's AFE is
disabled.
Same issues regarding cell voltage initialization issues
Nuvation Energy High-Voltage BMS - Product Manual
(Section
10.1.1.1)
84
Rev 1.2, 2021-03-03
Curie Update 1