3.2. Doorways

14 / 156
VARMAX 120 to 225 boilers fit through doors 700 mm wide with the casing
on (boiler with doors and side jackets).
VARMAX 275 to 320 boilers fit through doors 735 mm wide without the casing
on (boiler without doors, without side jackets and without side insulating
panels).
However, it is possible to pass through the 700 mm doors if the following
parts are removed, in addition to the parts mentioned above:
• the two inspection doors with their 16 fastening clamps,
• the two lower hinge lugs of the front housing doors (with the step),
• the two upper hinge lugs of the front housing doors (with the step),
• all the cable clamps at the inlet of the high- and low- current wiring
gutter.
VARMAX 390 to 450 boilers fit through doors 800 mm wide without the casing
on, which means that the following parts must be removed:
• the two front housing doors,
• the side insulating jackets,
• the side insulating panels
• the two lower hinge lugs of the front housing doors (with the step),
• the two upper hinge lugs of the front housing doors (with the step),
• all the cable clamps at the inlet of the high- and low- current wiring
gutter.
VARMAX 525 to 600 boilers fit through doors 1100 mm wide without the
casing on, which means that the following parts must be removed:
• the two front housing doors,
• the side insulating jackets,
• the side insulating panels
• the two lower hinge lugs of the front housing doors (with the step),
• the two upper hinge lugs of the front housing doors (with the step),
• all the cable clamps at the inlet of the high- and low- current wiring
gutter.