12.3 Specifications of Expansion Units
12.3.1 Input Specifications of the 64-point Digital Input Unit
■
Input specifications
Item
Insulation method
Rated input voltage
Rated input current
Input impedance
Operating voltage range
Min. ON voltage / Min. ON current
Max. OFF voltage / Max. OFF
current
Response time
Input points per common
Operating mode indicator
External connection method
■
Internal circuit diagram of the 64-point digital input unit
● All COM terminals are connected within the unit.
WUME-GM1H-01
Specifications
Optical coupler
24 V DC
Approx. 2.7 mA (at 24 V DC)
Approx. 6.8 kΩ
20.4 to 26.4 V DC
19.2 V / 2.5 mA
5 V / 1.5 mA
0.2 ms max. (Possible to change by using the input time constant
OFF→ON
selection function)
0.2 ms max. (Possible to change by using the input time constant
ON→OFF
selection function)
32 points/1 common
Operating mode indicator: 32-point LED display (Lit when ON, SW
selection)
Connector connection (Compliant with the MIL standard, 40P, two pieces
used)
12.3 Specifications of Expansion Units