Components
2.16.2 Secondary swing flap motor
Checking procedures
To perform an electrical check of the swing flap motor
Repair procedures
To remove the swing flap motor gearcase assembly
Service manual
116
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Disconnect the motor connector from the indoor unit PCB.
2 Measure the resistance between the following pins of the motor connector.
The measurements MUST be as shown in the table below.
Pins
1-2
1-3
1-4
1-5
2-3
2-4
2-5
3-4
3-5
4-5
Swing flap motor resistance
measurements are correct?
Yes
No
INFORMATION
To replace the motor, the complete gearcase assembly MUST be replaced.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Remove the main swing flap from the indoor unit (by clicking it out).
2 Remove the secondary swing flap from the indoor unit (by clicking it out).
3 Remove the right side fan guard from the indoor unit (by clicking it out).
"2.13 Plate
Measured resistance (Ω)
235
470
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Replace the swing flap motor, see
"Repair
procedures" [
"2.13 Plate
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
4
work" [
99].
4
116].
4
work" [
99].
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02