Individual settings for AFP7RTD (settings per channel)
Unit memory
Name
address
UM00080
Conversion pro-
cessing
UM00090
UM000A0
UM000B0
UM000C0
UM000D0
UM000E0
UM000F0
UM00081
Range setting
UM00091
UM000A1
UM000B1
UM000C1
UM000D1
UM000E1
UM000F1
UM00082
Average pro-
cessing
UM00092
UM000A2
UM000B2
UM000C2
Offset/gain pro-
UM000D2
cessing
UM000E2
Scale conversion
UM000F2
UM00083
Limit alarm
UM00093
UM000A3
Maximum and
UM000B3
minimum value
UM000C3
hold
UM000D3
UM000E3
UM000F3
UM00084
Average count or
UM00094
time period
UM000A4
UM000B4
UM000C4
UM000D4
UM000E4
UM000F4
UM00085
Offset value
UM00095
UM000A5
UM000B5
UM000C5
UM000D5
UM000E5
UM000F5
74
The unit memory addresses are listed in ascending order for the supported
channels (e.g. first unit memory address applies to channel 0, second to
channel 1 etc.).
Default
16#1
16#1
16#0
16#0
16#0
16#0
16#0
200
0
Setting range
16#0: Disable
16#1: Enable
16#1: RTD input Pt100-1(-100.0°C to 200.0°C)
16#2: RTD input Pt100-2(-200.0°C to 650.0°C)
16#3: RTD input JPt100-1(-100.0°C to 200.0°C)
16#4: RTD input JPt100-2(-200.0°C to 650.0°C)
16#5: RTD input Pt1000-1(-100.0°C to 100.0°C)
Bit 0-3
16#0: Disable
16#1: Count-based average
16#2: Time-based average
16#4: Moving average
Bit 4–7
16#0: Disable
16#1: Enable
Bit 8–11
16#0: Disable
16#1: Enable
Bit 12–15
Not used
Bit 0-3
16#0: Disable
16#1: Enable
Bit 4–7
16#0: Disable
16#1: Enable
To apply the setting, an average processing method must
be enabled.
Count-based average: 2–60000
Time-based average: 200–60000ms
Moving average: 3–64
*)
(specified with an unsigned integer)
To apply the setting, "Offset/gain processing" must be
enabled.
Setting range: -3000 to +3000 (specified with a signed
integer)
FP7 Thermocouple and RTD Units User's Manual
*)