Unit configuration
AFP7RTD
42
General (common to all channels):
Item name
Power frequency
Channel 0-7 (settings per channel)
Item name
Conversion processing
Range setting
Average processing
Average count or time
period
Offset/gain processing
Offset value
Gain value
Limit alarm
High limit alarm
switch-on value
High limit alarm
switch-off value
Low limit alarm
switch-on value
Low limit alarm
switch-off value
Maximum and mini-
mum value hold
Data
60Hz/50Hz
Data
Enable/Disable
Pt100-1(-100°C..200°C)
Pt100-2(-200°C..650°C)
JPt100-1(-100°C..200°C)
JPt100-2(-200°C..650°C)
Pt1000-1(-100°C..100°C)
Disable/Count-based aver-
age/Time-based average/Moving
average
Count-based average: 2–60000
counts
Time-based average: 200–60000ms
Moving average: 3–64
Disable/Enable
-3000 to +3000
+9000 to +11000
Disable/Enable
-31250 to +31250
-31250 to +31250
-31250 to +31250
-31250 to +31250
Disable/Enable
FP7 Thermocouple and RTD Units User's Manual
Default setting
60Hz
Default setting
Enable
Pt100-1(-100°C..2
00°C)
Disable
8
200
8
Disable
0
10000
Disable
1000
1000
0
0
Disable