2-7 RTD Input Wiring

RTD connection are shown in Figure 2-6, with the compensating
lead connected to terminal 4. For two-wire RTD inputs, terminals 4
and 5 should be linked. The three-wire RTD offers the capability of
lead resistance compensation provided that the three leads are of
same gauge and equal length.
Two-wire RTD should be avoided, if possible, for the purpose of
accuracy. A 0.4 ohm lead resistance of a two-wire RTD will produce
1 degree C temperature error.