Unused control terminals should not be used as jumper
points as they may be internally connected, causing
damage to the unit.
*
Verify that the ratings of the output devices and the inputs
as specified in Chapter 6 are not exceeded.
*
Electric power in industrial environments contains a certain
amount of noise in the form of transient voltage and spikes.
This electrical noise can enter and adversely affect the
operation of microprocessor-based controls. For this
reason we strongly recommend the use of shielded
thermocouple extension wire which connects the sensor to
the unit. This wire is a twisted-pair construction with foil
wrap and drain wire. The drain wire is to be attached to earth
ground at the sensor end only.