5.2 System Startup

5.2.1 IR.LINK SUPPORT system startup procedure

[1]
Mount IR.LINK module
Set rotary switch
[2]
Start IR.LINK system
[3]
software
Edit IR.LINK module
[4]
[1] Power down the CPU and then mount the IR.LINK
module.
[2] (a) Set the MODU No. switch of the IR.LINK
module to 0 (main module) or 1 (sub-module).
(b) Use the BIT RATE switch of the IR.LINK
module to set the bit rate to 0 (1 Mbps), 1 (0.5
Mbps), 2 (0.25 Mbps), or 3 (0.125 Mbps).
[3] Connect the CPU-Windows personal computer and
then start the IR.LINK system software system.
[4] Edit the IR.LINK module refer to the SOFTWARE
MANUAL OPTION IR.LINK For Windows
(manual number SAE-3-155).