Fujitsu ARYG72LHTA Service Instruction page 90

Duct type inverter
Hide thumbs Also See for ARYG72LHTA:
Table of Contents

Advertisement

Setting the Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required.
Select the approriate control drtting according to the installed environment.
To change this setting, set Function 42 to Both "01".
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Setting Description
No correcion 00°C
More
Cooling
Less
Heating
Less
Cooling
More
Heating
Auto restart
Enable or disable automatic restart after a power interruption.
Setting Description
Enable
Disable
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.When operating by a concentration remoto controll, "Enable:00" that
and use it.
Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both"
(01).
Setting Description
Indoor Unit
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
No correcion
-0.5°C
-1.0°C
-1.5°C
-2.0°C
-2.5°C
-3.0°C
-3.5°C
-4.0°C
cooling)
+0.5°C
+1.0°C
+1.5°C
+2.0°C
+2.5°C
+3.0°C
+3.5°C
+4.0°C
03-03
(
Factory setting)
Function Number
Setting Value
35
36
(For
(For
heating)
(
Function Number
40
(
Function Number
42
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
Factory setting)
Setting Value
00
01
Factory setting)
Setting Value
00
01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aryg90lhtaAoyg72lrlaAoyg90lrla