Fujitsu ARYG72LHTA Service Instruction page 85

Duct type inverter
Hide thumbs Also See for ARYG72LHTA:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 8
Thermistor
Check Point : Check Thermistor resistance value
Remove connector and check Thermistor resistance value.
Temperature
[°C]
Thermistor A
- 20
---
- 10
---
- 5
---
0
168.6
5
129.8
10
100.9
15
79.1
20
62.6
25
49.8
30
40.0
40
26.3
50
17.8
60
12.3
70
8.7
80
6.3
90
4.6
100
3.4
110
2.6
120
2.0
Discharge temp. TH
Applicable
Compressor temp. TH
Thermistors
Resistance Value [ k ]
Thermistor B
Thermistor C
---
105.4
27.8
58.2
21.0
44.0
16.1
33.6
12.4
25.9
9.6
20.2
7.6
15.8
6.0
12.5
4.8
10.0
3.8
8.0
2.5
5.3
1.7
3.6
1.2
---
---
---
---
---
---
---
---
---
---
---
---
---
Heat exchanger. TH
Outdoor temp. TH
02-49
Thermistor D
---
27.4
20.7
15.8
12.2
9.5
7.5
5.9
4.7
3.8
2.5
1.7
1.2
0.8
0.6
0.4
0.3
---
---
Heat sink temp. TH

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aryg90lhtaAoyg72lrlaAoyg90lrla

Table of Contents