1-8. COMPRESSOR CONTROL

1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in Table 7.
(Table 7 : Compressor Operation Frequency Range)
ARTG72LHTA
ARTG90LHTA
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Fig.9.
(Fig.9 : Compressor Control at Start-up)
< Normal start-up >
Immediate start-up after power-ON (cooling)
(rps)
Upper
70
limit
speed
60
50
Immediate start-up after power-ON (Hearting Ta < 10°C)
(rps)
80
70
Upper
60
limit
speed
50
40
Immediate start-up after power-ON (Hearting Ta > 10°C)
(rps)
Upper
60
limit
speed
50
40
Cooling
Heating
Min
Max
Min
15rps
81rps
15rps
15rps
90rps
15rps
60
120
Elapsed time
720
840
Elapsed time
60
120
Elapsed time
01-11
Max
81rps
90rps
180
(sec)
960
1080
=
180
(sec)
1200
(sec)
Ta : Outdoor temperature