Long Term Storage Log - Emerson Vilter VSG128 Installation, Operation And Service Manual

Hpld single screw bare shaft compressor
Table of Contents

Advertisement

Long Term Storage Log

Company:
Serial Number:
Name (Please Print):
Date (M/D/Y):
PSI Nitrogen Pressure - Current
PSI Nitrogen Pressure - Recharged (If pressure is low, identify and fix leak prior to recharging, see Compressor Unit Leak Check
Nitrogen Leak Location (Briefly explain nature of leak):
Compressor Shaft (Rotate shafts at least 6 revolutions)
Motor Shaft (Rotate shafts at least 6 revolutions)
Motor Bearings Greased
Air Cooled Oil Cooler Rotated
Bare Metal Surfaces (Check all bare metal surfaces for rust and ensure they are covered with rust inhibitor)
Desiccants (Are desiccants still effective? If not, replace. Check control panel, motor, pneumatic controllers and valves)
Cover Bags/Tarp (Ensure bags and tarps are not torn and are sealed over components correctly, replace if damaged)
Valves (Stop valves are in closed position so the compressor unit is isolated. All other valves, except those venting and draining to atmo-
sphere are to be open)
Space Heater & Panel Components (Ensure space heater is energized and panel components are rust-free)
Name (Please Print):
Date (M/D/Y):
PSI Nitrogen Pressure - Current
PSI Nitrogen Pressure - Recharged (If pressure is low, identify and fix leak prior to recharging, see Compressor Unit Leak Check
Nitrogen Leak Location (Briefly explain nature of leak):
Compressor Shaft (Rotate shafts at least 6 revolutions)
Motor Shaft (Rotate shafts at least 6 revolutions)
Motor Bearings Greased
Air Cooled Oil Cooler Rotated
Bare Metal Surfaces (Check all bare metal surfaces for rust and ensure they are covered with rust inhibitor)
Desiccants (Are desiccants still effective? If not, replace. Check control panel, motor, pneumatic controllers and valves)
Cover Bags/Tarp (Ensure bags and tarps are not torn and are sealed over components correctly, replace if damaged)
Valves (Stop valves are in closed position so the compressor unit is isolated. All other valves, except those venting and draining to atmo-
sphere are to be open)
Space Heater & Panel Components (Ensure space heater is energized and panel components are rust-free)
procedure in Section 5)
procedure in Section 5)
Sales Order Number:
Initial:
Initial: