Technical Description; Construction; Functional Description; Normal Operation - oventrop Aktor M ST L Operating Instructions Manual

Electromotive actuator
Hide thumbs Also See for Aktor M ST L:
Table of Contents

Advertisement

"Aktor M ST L 24V"
3.

Technical description

3.1

Construction

64
Illust. 1: Side view
Illust. 2: Front view
3.2

Functional description

3.2.1

Normal operation

The actuator opens or closes the valve depending on
the applied control voltage.
The actuator can be adapted to the specific parame-
ters of the valve used with the help of DIP switches.
3.2.2

Emergency end position

The actuator features an energy store.
If the operating voltage fails, the stem of the actuator
101271784-V02.01.2020
86.5
M30x1.5
48.5
will move to the emergency end position (see section
6.3 on page 10).
3.3

Technical data

Operating voltage
24 V AC ±10 %; 50/60 Hz;
24 V DC ±10 %
Power consump-
Dimensioning: 6.8 VA (24 V
tion
AC);
3.3 W (24 V DC)
nominal: 5.3 VA (24 V AC);
2.7 W (24 V DC)
Start up load
For short periods max. 12 A
Drive
Steady control 0 - 10 V DC;
<  0 .5 mA
Connection
Fixed pre-assembled cable
1.5 m; 5 x 0.5 mm
Display
LED display for operating volt-
age and status
Motor deactiva-
Drive stem:
tion
- extending = load-depend-
- retracting = travel-depend-
Piston stroke
Max. 4 mm
Floating time
22 s/mm
Emergency float-
about 5 s/mm
ing time
Operating power
Nominal 150 N
Position indicator
Stroke scale
Position feedback 2 - 10 V; DC, 5 mA
for 0 -100 % travel
Emergency con-
Emergency end position ad-
justable
trol function
Valve anti-block-
Active
ing function
Permissible fluid
0 °C - 120 °C
temperature in the
valve
Ambient temper-
0 °C - 50 °C
ature
Ambient humidity
0 - 85% r.h., not condensing
Protection class
IP54
Protective system
Degree of protection
Installation posi-
360°
tion
Maintenance
maintenance-free
Weight
250 g