Startup Wizard; Pid And Advanced App. Startup - Emerson EVH Series Installation Manual

Variable frequency drive
Table of Contents

Advertisement

Startup Wizard Instructions
For any further explanations of the below items please see Emerson AE bulletin AE-1466. Information for Items 6-13 can be
found in Copeland Mobile or OPI for the specific compressor model. For general motors, on the nameplate.
Item
Description
1

Startup Wizard

2
Application
3
Language
4
Real Time Clock
5
Daylight Saving
6
Min Frequency
7
Max Frequency
8
Motor Nom Current
9
Current Limit
10
Motor Nom Speed
11
Motor PF
12
Motor Nom Voltag e
13
Motor Nom Frequency
14
Accel Time 1
15
Decel Time 1
16
Hand Control Place
17
Hand Reference
Press OK?
0 = basic
1 = PID
2 = Advanced
0 = English
1 = Chinese
2 = Deutsch
yy.mm.dd
hh:mm:ss
0 = Off
1 = EU
2 = US
Min: 0.00Hz
Max: Max Frequency
Min: Min Frequency
Max: 400. 00Hz
Min: 0.1A
Max: 500.0A
Min: Ih*1/ 10
Max: Ih*2
Min: Ih*1/ 10
Max: Ih*2
Min: 0.30
Max: 1.0
Min: 180V
Max: 690V
Min: 30.00 Hz
Max: 400. 00 Hz
Min: 0.1 sec
Max:3000.0 sec
Min: 0.1 sec
Max:3000.0 sec
0 = Keypad
1 = I/O Terminal Start 1
2 = I/O Terminal Start 2
3 = Feildbus
0 = AI1
13 = AI1 * AI2
1 = AI2
14 = AI1 or AI2
2 = Slot A: AI1
15 = Min(AI1,AI2)
3 = Slot B: AI1
16 = Max(AI1,AI2)
4 = AI1 Joystick
17 = PID1 Control Output
5 = AI2 Joystick
18 = PID2 Control Output
6 = Keypad
7 = Feildbus
9 = Max Fre quency
10 = AI1 + AI2
11 = AI1 - AI2
12 = AI2 - AI1
Item
Description
18
Auto 1 Control Place
19
Auto 1 Reference
20
Bypass Enabled
21
Application Mini-Wizard
Now the Startup Wizard is done. It wont show again on the
next power up. If you want to reset it, please set the Startup
Wizard (P13.1.17) or select it from the main menu screen to
enable and cycle the power to the drive.
PID and Advanced Application Mini-Wizard
The PID Mini-Wizard is activated in the Quick Setup menu.
This Wizard assumes that you are going to use the PID
controller in the "one feedback/one setpoint" mode. The
control place will be I/O A and the default process unit "%."
The PID Mini-Wizard asks for the following values to be set:
PID Mini-Wizard values
Item
Description
20
PID 1 Process Unit
21
PID1 Process Unit Min
22
PID1 Process Unit Max
23
PID 1 Set Point 1 Source
24
PID 1 Keypad Set Point 1
25
PID 1 Feedback 1 Source
26
PID 1 Feedback 1 Min
27
PID 1 Feedback 1 Max
0 = I/O terminal Start 1
1 = Fieldbus
2 = I/O terminal start 2
3 = Keypad
0 = AI1
1 = AI2
2 = Slot A: AI1
3 = Slot B: AI1
4 = AI1 Joystick 5
= AI2 Joystick 6 =
Keypad
7 = Feildbus
9 = Max Frequency
10 = AI1 + AI2
11 = AI1 - AI2
12 = AI2 - AI1
13 = AI1 * AI2
14 = AI1 or AI2
15 = Min(AI1,AI2)
16 = Max(AI1,AI2)
17 = PID1 Control Output
18 = PID2 Control Output
0 = Disabled
1 = Enabled
Press OK?
Select Units
Min: –99999.99
Max: PID1 Process Unit Max
Min: PID1 Process Unit Min
Max:
99999.99
Select Function
Min: PID 1 Process Unit Min
Max: PID 1 Process Unit Max
Select Input
Min: –200%
Max: 200%
Min: –200%
Max: 200%
34

Advertisement

Table of Contents
loading

Table of Contents