Contents; Protection Features - Kaco blueplanet 87.0 TL3 Manual

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

2 | Safety
The device is intended for indoor and outdoor applications and may only be used in countries for which it has
been approved or for which it has been released by KACO new energy and the grid operator.
Operate the device only with a permanent connection to the public power grid. The country and grid type se-
lection must be commensurate with the respective location and grid type.
The requirements of the grid operator must be met for grid connection to take place. The permission of the rel-
evant authorities may also be required in order to secure authorisation to connection to the grid.
The enclosed documentation is an integral part of the product. The documentation must be read, observed and
stored in a place which is freely accessible at all times.
The name plate must be permanently attached to the product.
Any other or additional use of the device shall be regarded as improper.
This includes:
– Use of a distribution system that is not described (grid type)
– Use of sources other than PV-strings.
– Mobile use
– Use in rooms where there is a risk of explosion
– Use in direct sunlight, rain or a storm or other harsh environmental conditions
– Outdoor use in environmental conditions that exceed the limits stated in the technical specifications >En-
vironmental data.
– Operation outside the specification intended by the manufacturer
– Overvoltage on the DC connection of over 1,500 V
– Modifying the device
– Standalone mode
2.2

Protection features

The following monitoring and protection functions are built-in:
– RCMU (Residual Current Monitoring Unit)
– Overvoltage conductor / varistor to protect the power semiconductors from high-energy transients on the
grid and generator sides.
– Device temperature monitoring system
– EMC filter to protect the inverter from high-frequency grid interference
– Grid-side varistors grounded to earth to protect the product against burst and surge pulses
– Anti-islanding detection according to the current standards.
– Isolation detection / residual current monitoring and disconnection function to detect isolation faults
NOTE
If the device is connected, the overvoltage conductors / varistors contained in the device have an impact on the
electrical system insulation resistance test as per HD 60364-6 / IEC 60364-6 Low-voltage installations- Part 6:
Verification.
IEC 60364-6 6.4.3.3 describes two options for this case. The first option is to disconnect devices with an over-
voltage conductor or, if this is not practicable, then the test voltage can be reduced to 250V.
2
WARNING! The device is not intended for use in residential areas and cannot ensure adequate
protection of radio reception in such environments.
Page 8
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO blueplanet 110 TL3
KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3 KACO blueplanet 155 TL3
Manual
2
KACO blueplanet 165 TL3

Advertisement

Table of Contents
loading

Table of Contents