LG ARTCOOL Series Service Manual page 17

Inverter type room air conditioner
Hide thumbs Also See for ARTCOOL Series:
Table of Contents

Advertisement

Part 2 Functions & Controls
4.8 Preheat
• This is operation to preheat the compressor by conducting current through motor coils of the compressor for preventing
phenomena that liquid refrigerants are income due to difference between temperature of the outside pipe and tempera-
ture of the compressor as outdoor temperature becomes low.
• Enter preheat operation of the compressor if meeting
where outdoor temperature is less than 5°C
where discharge temperature of the compressor is more than 15°C
where the compressor turns off
• Release preheat operation if meeting one or more of
where outdoor temperature is more than 5°C
where diacharge temperature of the compressor is more than 25°C
where the compressor turns on
COMP
Discharge Temerature
15˚C
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
,
,
conditions as below at the same time.
,
,
conditions.
Preheat Off
Preheat On
- 16 -
25˚C
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents